Skip to main content
Siemens 3RV2711-0GD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2711-0GD10 SIRIUS Circuit Breaker, S00, 100 kA SC

MPN3RV2711-0GD10
Active

Siemens SIRIUS, circuit breaker, size S00, 3RV2711-0GD10, 100 kA interrupting capacity at 240-690 V AC, screw and snap-on mounting on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2711-0GD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-0GD10 — Electrical
ParameterValue
Rated operational current (Ie)0.63 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2711-0GD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current8.2 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-0GD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-0GD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-0GD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-0GD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-0GD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

This is a Siemens SIRIUS 3RV2711-0GD10 circuit breaker in the compact S00 frame size, designed for system protection under UL 489 and CSA C22.2 No. 5. It's the kind of breaker you'd spec into a motor branch circuit or distribution panel where you need a high fault-current rating — it carries 100 kA interrupting capacity all the way from 240 V up through 690 V AC.

Clearance requirements are 70 mm above and below, 30 mm to the sides, and zero forward clearance, so you can tuck it tight against a gland plate or back panel. Any mounting position works.

Terminals and wiring

The screwdriver spec is a Pozidriv size 2 tip with a 5-6 mm shaft diameter. Main contact terminal size is M4. That's a standard industrial panel wire range; no oddball metric that needs a special ferrule.

Frequently asked questions

What is the interrupting capacity of the 3RV2711-0GD10?

It carries 100 kA interrupting capacity at 240 V, 400 V, 500 V, and 690 V AC. That's the same rating across the full voltage range — no derating as voltage climbs.

What are the mounting dimensions for this circuit breaker?

The S00 frame measures 45 mm wide, 97 mm deep, and 144 mm tall. It snaps onto a 35 mm DIN rail per DIN EN 60715, with 70 mm clearance above and below, 30 mm to the sides, and zero forward clearance needed.

Where can I buy the 3RV2711-0GD10?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an inquiry for a firm offer.

MPN
3RV2711-0GD10