Skip to main content
Siemens 3RV2711-0HD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2711-0HD10 SIRIUS Circuit Breaker, S00, 100 kA

MPN3RV2711-0HD10
Active

Siemens SIRIUS circuit breaker, size S00, 3RV2711-0HD10, 100 kA interrupting rating at 400 V AC, screw and snap-on 35 mm DIN rail mounting, UL 489/CSA design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2711-0HD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-0HD10 — Electrical
ParameterValue
Rated operational current (Ie)0.8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2711-0HD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current10 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-0HD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-0HD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-0HD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-0HD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-0HD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

The Siemens 3RV2711-0HD10 is a SIRIUS circuit breaker in size S00, designed for system protection per UL 489 and CSA C22.2 No. 5. The interrupting rating is a flat 100 kA across the board — 240 V, 400 V, 500 V, and 690 V AC — which means it clears faults up to that level without cascading upstream, regardless of the service voltage. That is unusual for a compact S00 frame and simplifies coordination studies: one SCCR number for the whole panel. Rated operating voltage spans 20 to 690 V, so it covers 400 V three-phase distribution and 690 V industrial supplies off the same order code. The AC-3 maximum switching frequency is 15 operations per hour — sized for motor starting duty, not continuous resistive switching.

No NRND flag, no last-time-buy window. The SIRIUS S00 platform is widely specified in European and North American panels, so the supply channel is stable.

Integration and mounting notes

The S00 frame measures 45 mm wide by 144 mm tall by 97 mm deep — that depth is the body only; forward clearance is 0 mm, so no extra space needed in front of the rail. Upwards clearance 70 mm, downwards 70 mm, sideways 30 mm. Screw terminals with a Pozidriv size 2 tip and a 5 to 6 mm screwdriver shaft diameter. Mounting position is any — vertical, horizontal, or inverted — no derating for orientation.

The main contacts are rated for 100,000 typical mechanical operations. No ground fault detection and no phase failure detection built in.

Frequently asked questions

Will 3RV2711-0HD10 drop into a panel specified around 3RV2011-0AA10?

Both are S00 frame size on 35 mm DIN rail, so the physical footprint matches — same width, height, and mounting clip. The 3RV2711-0HD10 carries a 100 kA interrupting rating versus the 3RV2011-0AA10's lower rating, so verify the panel's SCCR requirement before swapping.

MPN
3RV2711-0HD10