Siemens 3RV2711-1BD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2711-1BD10 SIRIUS Circuit Breaker, 100 kA at 400

MPN3RV2711-1BD10
Active

Siemens SIRIUS circuit breaker, 3RV2711-1BD10, size S00, 45 mm wide, 100 kA breaking capacity at 400 V AC, screw and snap-on 35 mm DIN rail mount, for system protection per UL 489.

$69.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2711-1BD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-1BD10 — Electrical
ParameterValue
Rated operational current (Ie)2 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2711-1BD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current26 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-1BD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-1BD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-1BD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-1BD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-1BD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

The Siemens 3RV2711-1BD10 is a SIRIUS circuit breaker, size S00, designed for system protection according to UL 489 and CSA C22.2 No. 5. That means it's built to serve as a branch-circuit protective device in North American panels — not just a motor-protective overload relay, but a listed breaker that clears faults upstream of the load.

At 400 V AC this breaker is rated 100 kA interrupting capacity. That's the same at 240 V AC and 500 V AC — 100 kA each — so it handles high-available-fault panels without cascading upstream. The breaker also lists backup fuse requirements: gG 25 A at 400 V and 500 V, gG 20 A at 690 V. If you're coordinating with upstream fuses, those are the maximum ratings for the backup protection to hold the breaker's SCCR.

The screwdriver shaft diameter is 5 to 6 mm, Pozidriv size 2. Main contact terminals use M4 screws.

Frequently asked questions

How do I get current pricing and availability for 3RV2711-1BD10?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is 3RV2711-1BD10's listed depth and width?

Depth is 97 mm, width is 45 mm, height is 144 mm. The 45 mm width is the same as the S00 frame size standard.

What compliance documentation does this brand provide for 3RV2711-1BD10?

The breaker is designed for system protection according to UL 489 and CSA C22.2 No. 5. Standard SIRIUS documentation includes RoHS and REACH declarations; specific certificates are available on request.

MPN