Skip to main content
Siemens 3RV2711-1CD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2711-1CD10 SIRIUS Circuit Breaker, 100 kA at 400

MPN3RV2711-1CD10
Active

Siemens SIRIUS, circuit breaker, 3RV2711-1CD10, S00 frame, 100 kA at 400 V AC, screw and snap-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2711-1CD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-1CD10 — Electrical
ParameterValue
Rated operational current (Ie)2.5 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2711-1CD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current33 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-1CD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-1CD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-1CD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-1CD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-1CD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

The Siemens 3RV2711-1CD10 is a SIRIUS S00 circuit breaker for system protection, designed per UL 489 and CSA C22.2 No. 5. It mounts on 35 mm DIN rail (DIN EN 60715) via screw or snap-on — the S00 frame keeps the width at 45 mm, so it fits standard 45 mm-per-pole spacing in a motor control center or distribution panel. Rated operating voltage spans 20 to 690 V. The interrupting ratings are the headline: 100 kA at 240 V, 400 V, and 500 V AC; 10 kA at 690 V AC.

Dimensions: 45 mm wide, 144 mm tall, 97 mm deep. That 97 mm depth is the body plus terminals — check gland-plate clearance if the panel is shallow, but the zero forward clearance means it doesn't protrude past the DIN rail front edge. Terminals are M4 screw-type for the main circuit, accepting 1 to 10 mm² solid/stranded, up to 2×10 mm². Screwdriver spec: Pozidriv #2, shaft diameter 5–6 mm. Mounting position any — no derating for horizontal or inverted install.

Frequently asked questions

Where can I buy 3RV2711-1CD10 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here.

What is the breaking capacity of 3RV2711-1CD10 at 400 V?

100 kA at 400 V AC — that's the interrupting rating for a bolted fault on a 400 V bus.

What compliance documentation does this breaker carry?

Designed for system protection per UL 489 and CSA C22.2 No. 5. The SIRIUS series typically ships with RoHS and REACH declarations; confirm with the order.

Will 3RV2711-1CD10 drop into a panel specified for 3RV2311-1CC10?

Both are S00 frame breakers on 35 mm DIN rail with the same 45 mm width and M4 screw terminals, so the mechanical fit and wiring are identical. The difference is in the interrupting rating and trip curve — verify the 3RV2311-1CC10's specs against your fault current before swapping.

MPN