Siemens 3RV2711-1DD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2711-1DD10 SIRIUS Circuit Breaker, S00, 100 kA at

MPN3RV2711-1DD10
Active

Siemens SIRIUS S00 circuit breaker 3RV2711-1DD10, for system protection per UL 489/CSA C22.2 No. 5, 100 kA interrupting capacity at 400 V AC, 45 mm wide, screw and snap-on 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2711-1DD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-1DD10 — Electrical
ParameterValue
Rated operational current (Ie)3.2 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2711-1DD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current42 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-1DD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-1DD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-1DD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-1DD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-1DD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

The Siemens 3RV2711-1DD10 is a SIRIUS S00 frame circuit breaker designed for system protection per UL 489 and CSA C22.2 No. 5. Rated interrupting capacity hits 100 kA at 240 V, 400 V, and 500 V AC, dropping to 10 kA at 690 V AC. Backup fuse coordination is specified: gG 32 A at 400 V and 500 V, gG 25 A at 690 V.

Integration & Clearances

Dimensions: 97 mm deep, 45 mm wide, 144 mm high. Required clearance above and below the unit is 70 mm; 30 mm to the side. No clearance needed forward or backward. M4 terminal screws, Pozidriv size 2 driver tip.

Frequently asked questions

What is the interrupting capacity of 3RV2711-1DD10 at 400 V?

100 kA at 400 V AC, which means it can safely interrupt a fault current up to that level without upstream devices needing to clear the fault.

Will 3RV2711-1DD10 drop into a panel specified around 3RV2021-1FA15?

Both are SIRIUS S00 frame breakers on 35 mm DIN rail, so the mounting footprint and width are compatible. However, verify the interrupting capacity and backup fuse coordination for your specific fault level — the 3RV2711-1DD10 is designed for system protection per UL 489, while the 3RV2021-1FA15 may be a different variant. Check your BOM for the exact ratings required.

Where can I buy 3RV2711-1DD10?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
3RV2711-1DD10