Specifications

3RV2711-1HD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-1HD10 — Electrical
ParameterValue
Rated operational current (Ie)8 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV2711-1HD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current104 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-1HD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-1HD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-1HD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-1HD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-1HD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

System-protection circuit breaker for the panel builder

The Siemens 3RV2711-1HD10 is a SIRIUS circuit breaker in size S00, designed specifically for system protection per UL 489 and CSA C22.2 No. 5 — meaning it serves as a branch-circuit protective device, not a motor-protective device. Its interrupting ratings are the headline: 100 kA at 240 V AC, 100 kA at 400 V AC, 42 kA at 500 V AC, and 6 kA at 690 V AC. Back-up fuse requirements are specified: gG 50 A at 400 V, gG 40 A at 500 V, gG 35 A at 690 V. If you are feeding this breaker from a transformer or a bus with higher prospective fault current, those fuse ratings define the maximum upstream protection that still lets the breaker do its job.

Integration into the panel — DIN rail and clearances

Clearance requirements: 70 mm upwards and downwards, 30 mm at the side, 0 mm forwards and backwards. The screwdriver shaft needs a 5–6 mm diameter, Pozidriv size 2 tip.

Frequently asked questions

Will 3RV2711-1HD10 drop into a panel specified around 3RV2411-1HA20 without rewiring?

Both are S00-size SIRIUS breakers with the same 45 mm width and DIN-rail mounting, so the physical swap is straightforward. However, the 3RV2411-1HA20 is a motor-protective breaker (overload + short-circuit), while the 3RV2711-1HD10 is a system-protection breaker (UL 489) — verify the branch-circuit protection scheme before substituting.