3RV2711-1JD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2711-1JD10 — Electrical
ParameterValue
Rated operational current (Ie)10 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)9.25 W
Power loss, per pole (AC, hot)3.1 W
3RV2711-1JD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current130 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)42 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2711-1JD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2711-1JD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2711-1JD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2711-1JD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2711-1JD10 — Specifications
ParameterValue
Design Of The ProductFor system protection according to UL 489/CSA C22.2 No. 5

Product details

The Siemens 3RV2711-1JD10 is a SIRIUS circuit breaker in frame size S00, designed for system protection per UL 489 and CSA C22.2 No. 5. Breaking capacity is the headline here: 100 kA at both 240 V and 400 V AC, dropping to 42 kA at 500 V and 6 kA at 690 V AC.

Dimensions: 97 mm deep, 45 mm wide, 144 mm tall. That side clearance is tighter than some breakers; verify adjacent device spacing if packing the rail. Use a Pozidriv size 2 tip with a 5–6 mm diameter shaft. Terminal torque isn't listed here, but the M4 thread on the main contacts is standard for this frame class.

Frequently asked questions

What is the breaking capacity of 3RV2711-1JD10 at 400 V?

100 kA at 400 V AC, which is the same rating as at 240 V. It drops to 42 kA at 500 V and 6 kA at 690 V AC.

Will 3RV2711-1JD10 fit on a standard DIN rail?

Yes, it mounts on 35 mm DIN rail per DIN EN 60715 using screw and snap-on fastening. The 45 mm width occupies one modular unit.

Where can I buy 3RV2711-1JD10 and get current pricing?