Skip to main content
Siemens 3RV2811-0DD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2811-0DD10 SIRIUS Circuit Breaker, 100 kA at 400

MPN3RV2811-0DD10
Active

Siemens SIRIUS, circuit breaker, 3RV2811-0DD10, 100 kA breaking capacity at 400 V AC, S00 frame size, screw and snap-on mounting onto 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2811-0DD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2811-0DD10 — Electrical
ParameterValue
Rated operational current (Ie)0.32 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2811-0DD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current6.5 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2811-0DD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2811-0DD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2811-0DD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2811-0DD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2811-0DD10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection according to UL 489/CSA C22.2 No.5

Product details

The Siemens 3RV2811-0DD10 is a SIRIUS circuit breaker in the S00 frame size, designed specifically for transformer protection per UL 489 and CSA C22.2 No. 5. That design designation means the thermal and magnetic trip curves are shaped to handle transformer inrush without nuisance tripping — a different profile from a standard motor-protective breaker.

Breaking capacity — what 100 kA means here

This breaker carries a 100 kA interrupting rating at 240 V, 400 V, 500 V, and 690 V AC. That is a flat 100 kA across the entire common industrial voltage range — you do not need to derate the fault-interrupt capability as line voltage rises. For a transformer primary circuit, that matters: a large transformer can feed a sustained fault current well above 50 kA, and this breaker clears it without cascading upstream. The rated operational voltage for AC-3 motor-switching duty is 690 V maximum, but the transformer-protection design is the primary role here.

Dimensions: 97 mm deep, 45 mm wide, 144 mm tall. That zero forward clearance is useful in a tight enclosure; the breaker can sit flush against the back panel or a gland plate. Screw terminals with M4 bolts; Pozidriv size 2 tip, shaft diameter 5 to 6 mm.

Environmental tolerance

That -20 °C floor is fine for most indoor industrial panels; if the enclosure sits in an unheated warehouse in a cold climate, verify the ambient stays above that during operation. No ground-fault or phase-failure detection built in — this is a straight thermal-magnetic breaker, not an electronic protection relay.

Frequently asked questions

Where can I buy the 3RV2811-0DD10?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What compliance documentation is available for this breaker?

The breaker is designed to UL 489 and CSA C22.2 No. 5 for transformer protection. Standard Siemens SIRIUS documentation includes CE declaration of conformity, RoHS, and REACH compliance data available on request.

MPN