Skip to main content
Siemens 3RV2811-0GD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2811-0GD10 SIRIUS Circuit Breaker, 100 kA SCCR, S

MPN3RV2811-0GD10
Active

Siemens SIRIUS circuit breaker, size S00, for transformer protection per UL 489/CSA C22.2 No.5, 100 kA SCCR at 400 V AC, screw and snap-on 35 mm DIN rail mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV2811-0GD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2811-0GD10 — Electrical
ParameterValue
Rated operational current (Ie)0.63 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)5.5 W
Power loss, per pole (AC, hot)1.8 W
3RV2811-0GD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current13 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)100 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V100 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2811-0GD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2811-0GD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2811-0GD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2811-0GD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2811-0GD10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection according to UL 489/CSA C22.2 No.5

Product details

Transformer-protection breaker with 100 kA SCCR headroom

The Siemens 3RV2811-0GD10 is a SIRIUS S00 circuit breaker designed specifically for transformer protection, complying with UL 489 and CSA C22.2 No.5. Its 100 kA short-circuit current rating holds across the full voltage range — 240 V, 400 V, 500 V, and 690 V AC — so you don't need to derate the interrupting capacity when the transformer feeds a higher-voltage secondary. That SCCR headroom simplifies coordination downstream: the breaker can clear a bolted fault without cascading upstream, which matters when the panel feeds a critical process line. The S00 frame (97 mm deep, 45 mm wide, 144 mm tall) mounts via screw fixing or snaps onto a standard 35 mm DIN rail per DIN EN 60715. Terminal screws accept 1 to 10 mm² solid or stranded, up to 2×10 mm², with a Pozidriv #2 driver. That footprint fits a standard 45 mm-wide DIN slot — no panel mods needed to swap in from a similar S00 frame.

Clearance and mounting

Mounting position is any orientation. That 70 mm vertical gap is the one to watch in a crowded panel — if you're stacking breakers, leave at least that much breathing room for heat dissipation and arc-fault venting.

Environmental and auxiliary specs

The breaker has no ground-fault or phase-failure detection built in — those functions are handled externally if needed. Main contact screw terminals take an M4 screw. Mechanical endurance of the main contacts is rated at 100,000 typical cycles, and the maximum switching frequency under AC-3 duty is 15 operations per hour.

Frequently asked questions

Where can I buy 3RV2811-0GD10 and get a price?

We source and quote this part to order against an RFQ. Submit a request through the storefront; availability and current pricing are confirmed at quote time.

Will 3RV2811-0GD10 drop into a panel specified around 3RV2011-0AA10?

Both are S00 frame breakers with the same 45 mm width and 35 mm DIN rail mounting, so the physical swap is straightforward — no panel modification needed. However, the 3RV2811-0GD10 is designed specifically for transformer protection (UL 489), while the 3RV2011-0AA10 is a general-purpose motor-protective breaker. Verify that the trip curve and SCCR requirements match your transformer application before substituting.

What compliance documentation does Siemens provide for 3RV2811-0GD10?

The breaker is designed to UL 489 and CSA C22.2 No.5 for transformer protection. Standard Siemens documentation includes the declaration of conformity (CE), RoHS and REACH compliance statements, and the product datasheet. Specific certificates are available on request.

MPN
3RV2811-0GD10