Skip to main content
Siemens 3RV2811-1CD10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2811-1CD10 SIRIUS Circuit Breaker, 100 kA SCCR, S

MPN3RV2811-1CD10
Active

Siemens SIRIUS 3RV2811-1CD10 circuit breaker, size S00, screw and snap-on 35 mm DIN rail mounting, for transformer protection per UL 489, 100 kA SCCR at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2811-1CD10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2811-1CD10 — Electrical
ParameterValue
Rated operational current (Ie)2.5 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2811-1CD10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current52 A
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)10 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V10 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionNo
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2811-1CD10 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
3RV2811-1CD10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded1 ... 10 mm², max. 2x 10 mm²
Conductor cross-section, finely stranded with ferrule1 ... 16 mm², max. 6 + 16 mm²
Conductor range, AWG (main contacts)2x (14 ... 10)
3RV2811-1CD10 — Mechanical
ParameterValue
Height144 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2811-1CD10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2811-1CD10 — Specifications
ParameterValue
Design Of The ProductFor transformer protection according to UL 489/CSA C22.2 No.5

Product details

The Siemens SIRIUS 3RV2811-1CD10 is a size S00 circuit breaker designed specifically for transformer protection, complying with UL 489 and CSA C22.2 No.5.

SCCR and selectivity

Rated short-circuit breaking capacity reaches 100 kA at 240 V, 400 V, and 500 V AC, dropping to 10 kA at 690 V AC. The gG fuse coordination values are 25 A at 400 V and 500 V, and 20 A at 690 V.

Integration notes

Clearance requirements: 70 mm upward and downward, 30 mm to the side, zero forward or backward. The screwdriver shaft must be 5 to 6 mm diameter with a Pozidriv size 2 tip. Main contact terminal screws are M4.

Frequently asked questions

What is the SCCR of 3RV2811-1CD10 at 400 V?

100 kA at 400 V AC, which means it safely interrupts faults up to 100,000 A at that voltage without cascading upstream.

Where can I buy 3RV2811-1CD10?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the mounting clearances for 3RV2811-1CD10?

70 mm upward and downward, 30 mm to the side, zero forward or backward. The breaker mounts on a 35 mm DIN rail per DIN EN 60715.

MPN