Siemens 3RV2902-4DF0 SIRIUS Shunt Release, 90-110 V AC, 50/6

MPN3RV2902-4DF0

Siemens SIRIUS shunt release 3RV2902-4DF0, 90-110 V AC 50/60 Hz coil, for 3RV2 motor circuit breakers sizes S00, S0, S2, S3.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2902-4DF0 — Identification
ParameterValue
SeriesSIRIUS
Product designationshunt release
Frame sizeS00, S0, S2, S3
3RV2902-4DF0 — Electrical
ParameterValue
Rated insulation voltage (Ui), pollution degree 3690 V
3RV2902-4DF0 — Mechanical
ParameterValue
Height90 mm
Width18.5 mm
Depth68 mm
Mounting methodsnap-on mounting
3RV2902-4DF0 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C

Product details

The 18.5 mm width matches the standard modular spacing of the 3RV2 breaker it mounts alongside, so it occupies a single 18 mm slot in the panel layout. The front face is finger-safe per IEC 60529, with IP00 protection class on the front — meaning the panel enclosure provides the environmental seal, not the release itself. Ring cable lug connection is specified for the coil wiring, consistent with the 3RV2 breaker terminal design.

For BOM freeze or PCN-watch scenarios, this part is a stable line item.

Rated insulation voltage is 690 V AC at pollution degree 3, which covers the majority of 400/480 V motor control panels without derating. Operating temperature range is -20 to +60 °C; storage range extends to -50 to +80 °C.

Frequently asked questions

Where can I buy the 3RV2902-4DF0?

This shunt release is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the coil voltage ratings for this shunt release?

The coil is rated 90-110 V AC at 50/60 Hz for continuous duty (100% on-period). It also supports 70-190 V AC for a 5-second on-period, and 70-190 V AC at 50/60 Hz for a 5-second on-period.