Skip to main content
Siemens 3RV2921-2M — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2921-2M SIRIUS Signaling Switch, 1 NO + 1 NC, Spr

MPN3RV2921-2M
Active

Siemens SIRIUS signaling switch, 3RV2921-2M, separate tripped signal and short-circuit alarm, 1 NO + 1 NC, spring-loaded terminals, for 3RV2 breakers sizes S00/S0/S2/S3.

$11.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV2921-2M — Identification
ParameterValue
SeriesSIRIUS
Product designationsignaling switch
Frame sizeS00, S0, S2, S3
3RV2921-2M — Connections
ParameterValue
Conductor cross-section, solid / stranded0.5 ... 2.5 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²)
3RV2921-2M — Mechanical
ParameterValue
Height90 mm
Width18 mm
Depth68 mm
Mounting methodplug-in fixing
3RV2921-2M — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
3RV2921-2M — Specifications
ParameterValue
Design Of The Productseparate tripped signal and short circuit alarm, 1 NO + 1 NC each

Product details

The Siemens SIRIUS 3RV2921-2M is a signaling switch designed as a bolt-on accessory for 3RV2 motor-protective circuit breakers. It provides a separate tripped signal and short-circuit alarm through one NO and one NC instantaneous contact each, giving the panel a clean way to distinguish a thermal overload trip from a short-circuit event without adding a separate monitoring relay.

Mounts via plug-in fixing directly onto 3RV2 breakers in frame sizes S00, S0, S2, and S3 — no DIN rail space consumed beyond the breaker itself. Spring-loaded terminals accept 0.5 to 2.5 mm² solid or stranded, or 2x (0.5 to 1.5 mm²) with ferruled ends. The 18 mm width keeps the assembly tight on the rail.

Contact ratings span the control-voltage range you'd expect on a motor branch: 2 A at 24 V, 0.5 A at 110 V, 0.25 A at 220/250 V, 4 A at 230 V, 3 A at 400 V, and 10 A at 690 V. The AC-12 maximum rating of 10 A covers resistive loads on the auxiliary circuit. These are the values that govern whether the signaling switch can handle the PLC input or indicator lamp load on your specific control voltage.

RoHS compliance date of October 1, 2009, covers EU substance restrictions.

Frequently asked questions

What is 3RV2921-2M used for?

It mounts to a 3RV2 motor-protective circuit breaker to provide a separate tripped signal and short-circuit alarm via one NO and one NC contact each, so the control system can distinguish a thermal overload from a fault.

What wire sizes does the spring terminal accept?

Solid or stranded 0.5 to 2.5 mm², or 2x 0.5 to 1.5 mm² with ferruled ends. AWG 20 to 14 for the auxiliary contact circuit.

Where can I buy 3RV2921-2M?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery target.

MPN