Skip to main content
Siemens 3RV5031-4EA10 — Motor Protection Circuit Breakers (MPCB)

3RV5031-4EA10 SIRIUS Motor Protection Circuit Breaker, 32 A,

MPN3RV5031-4EA10

Siemens SIRIUS 3RV5031-4EA10 motor protection circuit breaker, size S2, 3-pole, 32 A rated operational current at 400 V AC-3, Class 10 thermal-magnetic trip, screw terminals, 55 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV5031-4EA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV5031-4EA10 — Electrical
ParameterValue
Rated operational current (Ie)32 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV5031-4EA10 — Protection & Tripping
ParameterValue
Overload release setting range22 ... 32 A
Instantaneous short-circuit trip current416 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV5031-4EA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.75 ... 25 mm²), 1x (0.75 ... 35 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.75 ... 16 mm²), 1x (0.75 ... 25 mm²)
3RV5031-4EA10 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Mounting positionany
3RV5031-4EA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV5031-4EA10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

It is rated 32 A operational current at 400 V AC-3 duty, so it directly protects a motor drawing that full-load current. The 55 mm width (three 18 mm pole pitches plus clearance) fits standard panel layouts. Terminal acceptance: up to 35 mm² solid or 25 mm² finely stranded with ferrules, with box-type screw terminals torqued to 3–4.5 N·m.

The headline 32 A at 400 V AC-3 is the motor-switching rating — the current the breaker can make and break under motor start conditions. The maximum operating voltage is 690 V, covering 400 V and 480 V line-to-line systems common in industrial plants. Surge voltage withstand is 6 kV, which aligns with IEC 60947-2 overvoltage category III for distribution-level coordination. Thermal overload release is adjustable via the front dial (not detailed in the spec excerpt, but standard on SIRIUS breakers). The magnetic short-circuit trip is fixed. Shock resistance is 25 g for 11 ms per IEC 60068-2-27. Installation altitude is limited to 2000 m above sea level without derating.

Frequently asked questions

What is 3RV5031-4EA10's listed depth (149 mm) on this component line?

The depth is 149 mm, measured from the front of the DIN rail to the farthest rear projection — relevant when sizing enclosure depth against back-panel clearance.

MPN
3RV5031-4EA10