The S2 frame is 55 mm wide, 140 mm tall, 149 mm deep — fits standard panel layouts. Clearance requirements: 50 mm above and below, 30 mm at the sides, 140 mm forward, zero backward. Main circuit connections are screw-type box terminals accepting 2×(0.75–25 mm²) solid/stranded or 1×(0.75–35 mm²); AWG equivalents 2×(18–2) or 1×(18–2). Torque range 3–4.5 N·m. Terminals arranged top and bottom for straightforward busbar or cable routing.
Relative humidity 10–95% during operation. Installation altitude up to 2,000 m above sea level. Shock resistance 25 g / 11 ms per IEC 60068-2-27. RoHS compliant with substance prohibition date July 1, 2006. Total typical power loss 20 W.