Siemens 3RV5331-4EC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV5331-4EC10 SIRIUS Circuit Breaker, 32 A AC-3, 690

MPN3RV5331-4EC10

Siemens SIRIUS, circuit breaker for starter combinations, size S2, 3-pole, 32 A AC-3 at 400 V, 690 V rated insulation, screw terminals, 35 mm DIN-rail mount, order code 3RV5331-4EC10.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV5331-4EC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV5331-4EC10 — Electrical
ParameterValue
Rated operational current (Ie)32 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV5331-4EC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current416 A
Short-circuit trip typemagnetic
Short-circuit protectionYes
3RV5331-4EC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.75 ... 25 mm²), 1x (0.75 ... 35 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.75 ... 16 mm²), 1x (0.75 ... 25 mm²)
3RV5331-4EC10 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Mounting positionany
3RV5331-4EC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV5331-4EC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

What the 32 A AC-3 rating means for your motor circuit

Its headline rating is 32 A operational current at AC-3 duty (400 V), which means it directly protects a motor drawing up to that current under the heaviest switching category — starting, running, and stopping induction motors with inrush. That 416 A threshold is fixed — not adjustable — so verify your motor's locked-rotor current stays above it to avoid nuisance trips on startup.

The S2 frame takes 55 mm width on the rail — three of these side-by-side fit in a standard 200 mm wide enclosure without crowding. Depth is 149 mm, so plan for at least 160 mm clear behind the panel door to allow wiring and cover clearance. The 15 W typical power loss at full load means no forced ventilation is needed in a standard IP54 enclosure, but cluster several breakers and the internal temperature rise needs checking against the -20 to +60 °C operating range.

Termination and wiring constraints

Screw-type box terminals on top and bottom accept 2 x (0.75 to 25 mm²) solid or stranded, or 1 x (0.75 to 35 mm²). For finely stranded with ferrules, capacity drops to 2 x (0.75 to 16 mm²) or 1 x (0.75 to 25 mm²). AWG equivalents: 2 x (18 to 2) or 1 x (18 to 2). Tightening torque: 3 to 4.5 N·m. That's a standard slot/Pozidriv #2 range — a torque screwdriver set to 4 N·m is the safe middle point. The terminals are rated for the full 32 A continuous; no derating needed for the termination itself, but the 15 W power loss is dissipated through the terminals and housing, so keep adjacent wiring bundles clear of the breaker body.

Operates in 10 to 95 % relative humidity and survives transport from -50 to +80 °C. Shock resistance: 25 g for 11 ms per IEC 60068-2-27 — rugged enough for machine-mounted panels near presses or conveyors. Installation altitude limit is 2 000 m above sea level; above that, derate the current per IEC 60947-2. The part carries a substance prohibition date of 07/01/2006, which aligns with the original EU RoHS compliance deadline — no lead, cadmium, or mercury above threshold. For UL/CSA listings, the SIRIUS family is typically UL 508 listed; confirm the specific file number at quote time if your panel requires a marked UL listing.

Frequently asked questions

What is the short-circuit trip threshold on this breaker?

The magnetic instantaneous short-circuit trip responds at 416 A. That is a fixed setting — not adjustable — and it is the value that coordinates with the downstream contactor's withstand rating in a starter combination.

Can I buy 3RV5331-4EC10 and what is the lead time?

We source this part to order against an RFQ. Availability and current pricing are confirmed at quote time — submit your quantity and target delivery date, and we will source it through our independent distribution network.

Will 3RV5331-4EC10 drop into a panel specified around 3RV6021-4DA10?

No — the 3RV5331-4EC10 is a size S2 frame with different terminal layout and trip characteristics than the S0-frame 3RV6021-4DA10. It is not a mechanical or electrical drop-in without rewiring and re-coordinating the motor branch circuit.

What compliance documentation is available for this part?

The part carries a substance prohibition date of 07/01/2006, consistent with original EU RoHS compliance. The SIRIUS family typically holds UL 508, CSA C22.2, and IEC 60947-2 approvals; confirm the specific certificate numbers at quote time for your jurisdiction.

MPN
3RV5331-4EC10