The instantaneous short-circuit trip responds at 975 A, clearing faults fast enough to protect downstream contactors and cables.
The S3 frame size (174 mm deep, 70 mm wide, 165 mm tall) fits standard panel layouts. Clearance: 50 mm above and below, 30 mm to the side for airflow and wiring access. Screw-type box terminals on top and bottom accept up to 70 mm² solid/stranded or 50 mm² fine-stranded with ferrules — torque to 4–6 N·m. Any mounting position works.