Skip to main content
Siemens 3RV5341-4MC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV5341-4MC10 SIRIUS Circuit Breaker, 100 A AC-3

MPN3RV5341-4MC10

Siemens SIRIUS 3RV5341-4MC10 circuit breaker for starter combinations, Size S3, 3-pole, 100 A at AC-3 400 V, screw terminals, magnetic short-circuit trip, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV5341-4MC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS3
3RV5341-4MC10 — Electrical
ParameterValue
Rated operational current (Ie)100 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV5341-4MC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current1 235 A
Short-circuit trip typemagnetic
Short-circuit protectionYes
3RV5341-4MC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (2.5 ... 16 mm²), 2x (10 ... 50 mm²), 1x (10 ... 70 mm²)
Conductor cross-section, finely stranded with ferrule2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
Conductor range, AWG (main contacts)2x (10 ... 1/0), 1x (10 ... 2/0)
3RV5341-4MC10 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth174 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV5341-4MC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV5341-4MC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

The magnetic instantaneous trip is fixed at 1 235 A, which coordinates with downstream contactors and overload relays per IEC 60947-4-1.

The S3 frame occupies 70 mm width on the rail, with 174 mm depth and 165 mm height. Clearance requirements: 50 mm upward, 167 mm forward, 0 mm backward, 50 mm downward, 30 mm at the side. These clearances matter for heat dissipation — the breaker dissipates 38 W total typical at full load, so adjacent devices need breathing room. Screw-type box terminals on top and bottom accept up to 70 mm² solid or stranded, or 2/0 AWG. Tightening torque is 4 to 6 N·m. For a panel wireman, that means the main power conductors land without adapter lugs up to fairly heavy cable — common for a 100 A motor branch.

This is the part to put on the BOM for a 100 A motor branch in a SIRIUS starter combination.

Relative humidity during operation: 10 to 95 %. Installation altitude maximum 2 000 m above sea level. Shock resistance per IEC 60068-2-27: 25g for 11 ms. The RoHS substance prohibitance date is July 1, 2006, confirming compliance with the original RoHS directive.

Frequently asked questions

What is the AC-3 motor rating of 3RV5341-4MC10?

It is rated 100 A at AC-3 duty at 400 V, which is the current it can switch motor loads up to under starting conditions per IEC 60947-4-1.

Where can I buy 3RV5341-4MC10?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What compliance documentation does Siemens provide for 3RV5341-4MC10?

The RoHS substance prohibitance date is July 1, 2006, confirming RoHS compliance. The part carries a 690 V rated insulation voltage per IEC 60947 and surge voltage resistance of 6 kV. Standard Siemens declarations of conformity and CE marking are available on request.

Will 3RV5341-4MC10 drop into a panel specified around 3RV6021-4DA10?

Both are SIRIUS circuit breakers on the 35 mm DIN rail footprint per DIN EN 50022, but the 3RV6021-4DA10 is a different frame size and current class. The 3RV5341-4MC10 is Size S3 with 70 mm width and 100 A AC-3 rating — verify panel cutout dimensions and busbar layout before substituting, as the mounting footprint and terminal positions differ.

MPN
3RV5341-4MC10