Skip to main content
Siemens 3RV5431-4AA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV5431-4AA10 SIRIUS Circuit Breaker, 16 A, Transfor

MPN3RV5431-4AA10

Siemens SIRIUS circuit breaker, 3RV5431-4AA10, 3-pole, 16 A rated operational current, Class 10, for transformer protection, 690 V, 50/60 Hz, S2 frame, screw terminals, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV5431-4AA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS2
3RV5431-4AA10 — Electrical
ParameterValue
Rated operational current (Ie)16 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV5431-4AA10 — Protection & Tripping
ParameterValue
Overload release setting range11 ... 16 A
Instantaneous short-circuit trip current325 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV5431-4AA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.75 ... 25 mm²), 1x (0.75 ... 35 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.75 ... 16 mm²), 1x (0.75 ... 25 mm²)
3RV5431-4AA10 — Mechanical
ParameterValue
Height140 mm
Width55 mm
Depth149 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
Mounting positionany
3RV5431-4AA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV5431-4AA10 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

Transformer-protection circuit breaker, 16 A, SIRIUS S2

The Siemens 3RV5431-4AA10 is a 3-pole SIRIUS circuit breaker purpose-designed for transformer protection, with a rated operational current of 16 A and a rated insulation voltage of 690 V. It carries a Class 10 trip characteristic, meaning the thermal overload release responds within 10 seconds at 7.2× the current setting — fast enough to protect a transformer winding from sustained overcurrent without nuisance-tripping on inrush. The magnetic short-circuit trip handles the high fault currents a transformer primary can see on a phase-to-phase bolted fault. Rated at 16 A in AC-3 duty at 400 V, this breaker switches motor loads up to that current, but its primary job is transformer primary-side protection where the inrush profile differs from a motor start. The S2 frame size keeps the unit compact enough for dense panel layouts while still accommodating screw-type box terminals that accept up to 35 mm² solid or 25 mm² finely stranded wire.

The 55 mm width and 149 mm depth fit standard S2 panel cutouts; clearance requirements are 50 mm upward, 50 mm downward, 140 mm forward, and 30 mm at the sides. Connections are top and bottom for the main circuit, with screw terminals torqued to 3–4.5 N·m. Operating temperature range is –20 to +60 °C with 10–95 % relative humidity, so it handles unconditioned industrial enclosures. Installation altitude is limited to 2 000 m above sea level without derating.

Electrical and environmental ratings

Rated operational voltage 690 V AC at 50/60 Hz. Shock resistance per IEC 60068-2-27 is 25 g for 11 ms. Typical power loss is 12 W total. The breaker provides both thermal overload protection (Class 10) and magnetic short-circuit protection in one unit.

Frequently asked questions

Where can I buy the 3RV5431-4AA10 and get a price?

The 3RV5431-4AA10 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the depth of the 3RV5431-4AA10?

The depth is 149 mm. Combined with a width of 55 mm and height of 140 mm, it fits the standard S2 frame footprint.

What compliance documentation does Siemens provide for the 3RV5431-4AA10?

The part carries a substance prohibition date of July 1, 2006, indicating RoHS compliance. Standard Siemens documentation includes the declaration of conformity and CE marking; specific UL/CSA certifications should be verified against the nameplate marking on the unit.

Will the 3RV5431-4AA10 drop into a panel specified around the 3RV6021-4DA10?

Both are SIRIUS S2 frame breakers with the same 55 mm width and DIN rail mounting, so the panel cutout and rail position are compatible. However, the 3RV5431-4AA10 is specifically designed for transformer protection (different trip curve tuning) versus the general motor-protection focus of the 3RV6021-4DA10. Verify the trip class and current rating match your load before substituting.

MPN
3RV5431-4AA10