Skip to main content
Siemens 3RV6011-0BA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6011-0BA10 SIRIUS Motor Protection Circuit Breake

MPN3RV6011-0BA10

Siemens SIRIUS motor protection circuit breaker, 3RV6011-0BA10, 3-pole, S00 size, 0.2 A rated operational current, Class 10 trip, 690 V AC-3 max, screw terminals, snap-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV6011-0BA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6011-0BA10 — Electrical
ParameterValue
Rated operational current (Ie)0.2 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6011-0BA10 — Protection & Tripping
ParameterValue
Overload release setting range0.14 ... 0.2 A
Instantaneous short-circuit trip current2.6 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6011-0BA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)
3RV6011-0BA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6011-0BA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6011-0BA10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

It combines a thermal overload release (Class 10) with a magnetic short-circuit trip in a single 45 mm-wide package. Rated at 0.2 A in AC-3 duty at 400 V, this breaker is sized for small motor loads — fractional-horsepower pumps, fans, or conveyor drives where the full-load current sits right at that 0.2 A mark.

The 45 mm width (one standard modular unit) and 96 mm depth fit neatly into a compact control panel — no extra space needed for side-by-side mounting as long as you respect the 30 mm side clearance to adjacent metalwork. Top and bottom entry for the main circuit conductors keeps wiring straight. Screw-type terminals accept up to 2× 4 mm² solid or stranded, or 2× 2.5 mm² with ferrule. Torque to 0.8–1.2 N·m — nothing exotic, just a standard screwdriver.

RoHS compliance date is May 1, 2012, and the part carries the usual Siemens industrial approvals.

If your motor nameplate says 0.18 A FLA, this breaker is the right call. The 15 operations per hour maximum at AC-3 keeps thermal buildup in check for normal start-stop cycles. Short-circuit breaking is handled by the magnetic trip, and the device is rated for a 6 kV surge voltage (impulse withstand). That 6 kV figure covers the transient environment of a standard industrial panel fed from a 400 V distribution transformer. Operating temperature range of -20 to +60 °C and 95% humidity tolerance mean it lives comfortably in a non-conditioned cabinet on the plant floor. Shock-rated to 25 g for 11 ms — tough enough for machine-mounted applications near presses or stamping equipment.

Frequently asked questions

Where can I buy 3RV6011-0BA10 and get a price?

It's sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no online stock number here, just a straight answer when you ask.

Will 3RV6011-0BA10 drop into a panel specified for 3RV6011-0CA10 without rewiring?

The 3RV6011-0CA10 is the same S00 frame, same 45 mm width, same DIN rail mount, same terminal arrangement. The difference is the current rating — the -0CA10 is a higher-current variant. If your wire sizes and terminal torque match the -0BA10's 0.2 A rating, the physical swap is clean. No rewiring needed.

What compliance documentation does Siemens provide for 3RV6011-0BA10?

The part is RoHS-compliant with a substance prohibition date of May 1, 2012. Standard Siemens industrial circuit breakers carry CE, UL, and CSA approvals per the SIRIUS family documentation. REACH compliance is covered under Siemens' standard declaration.