Siemens SIRIUS motor protection circuit breaker, 3RV6011-0DA15, 3-pole, 0.32 A rated operational current, Trip Class 10, 690 V AC-3, screw terminals, size S00, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RV6011-0DA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6011-0DA15 — Electrical
ParameterValue
Rated operational current (Ie)0.32 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6011-0DA15 — Protection & Tripping
ParameterValue
Overload release setting range0.22 ... 0.32 A
Instantaneous short-circuit trip current4.2 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6011-0DA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV6011-0DA15 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6011-0DA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6011-0DA15 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

It combines a thermal overload release (Trip Class 10) and a magnetic short-circuit release in a single 3-pole device, rated at 0.32 A operational current at 690 V AC-3.

The S00 frame occupies 45 mm width × 97 mm height × 96 mm depth.

Operating temperature range -20…+60 °C, storage/transport -50…+80 °C. Relative humidity 10…95% non-condensing. Shock resistance 25 g / 11 ms per IEC 60068-2-27. Surge voltage withstand 6 kV. Power loss 5 W typical at rated current. Maximum operating frequency 15 operations per hour at AC-3 duty — enough for a pump start/stop cycle, not for a rapid-reversing application.

MPN