Siemens 3RV6011-0FA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6011-0FA10 SIRIUS Motor Protection Circuit Breake

MPN3RV6011-0FA10

Siemens SIRIUS 3RV6011-0FA10 motor protection circuit breaker, size S00, 3-pole, 0.5 A rated operational current, Class 10 trip, 690 V, 50/60 Hz, screw-type terminals, screw and snap-on mounting onto 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6011-0FA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6011-0FA10 — Electrical
ParameterValue
Rated operational current (Ie)0.5 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6011-0FA10 — Protection & Tripping
ParameterValue
Overload release setting range0.35 ... 0.5 A
Instantaneous short-circuit trip current6.5 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6011-0FA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)
3RV6011-0FA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6011-0FA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6011-0FA10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV6011-0FA10 is a SIRIUS size S00 motor protection circuit breaker, designed for a 0.5 A rated operational current at 400 V AC-3 duty — that is the motor full-load current it protects, not a bus rating. The magnetic short-circuit trip acts instantaneously on a fault, and the breaker itself is rated for a 690 V maximum operating voltage across 50/60 Hz mains.

The S00 frame occupies 45 mm width, 97 mm height, and 96 mm depth — a compact footprint that leaves 50 mm clearance above and below, 30 mm to the sides, and zero forward/backward clearance required, so it packs tightly into a motor control centre sub-panel. Screw-type terminals on the main circuit accept up to 2× 4 mm² solid or stranded, torqued to 0.8–1.2 N·m.

Environmental and mechanical tolerance

Rated for operation from -20 to +60 °C with 10–95 % relative humidity, and transport down to -50 °C. Withstands 25 g shock for 11 ms per IEC 60068-2-27, and installation altitude is allowed up to 2 000 m above sea level — figures that cover most industrial enclosures and unpressurised plant rooms without derating.

Frequently asked questions

Where can I buy 3RV6011-0FA10 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3RV6011-0FA10's listed depth (96 mm) on this component line?

The depth is 96 mm, with a width of 45 mm and height of 97 mm. Clearance required: 50 mm above and below, 30 mm at the sides, zero forward or backward.

What compliance documentation does this brand provide for 3RV6011-0FA10 (RoHS, REACH, UL, IEC)?

The part carries a substance prohibitance date of 05/01/2012, indicating RoHS compliance. As a Siemens SIRIUS product, it is designed to IEC/EN 60947-2 and 60947-4-1 standards; UL and CSA approvals are typical for the series, though specific certification marks should be verified against the nameplate.

Will 3RV6011-0FA10 drop into a panel that was specified around 3RV6021-4DA10 without rewiring?

No — the 3RV6021-4DA10 is a different frame size and current rating (S2 vs S00), so the footprint, terminal spacing, and DIN-rail clip position differ. The 3RV6011-0FA10 will not mechanically interchange without panel rework.