DIN rail fit and panel space
Clearance: 50 mm above and below, zero sideways — so you can butt it against other S00 devices without extra spacing. Terminal capacity accepts 2x 0.75–2.5 mm² solid or stranded, or 2x 4 mm², with tightening torque 0.8–1.2 N·m.
Class 10 trip means it will disconnect before the motor windings overheat under locked-rotor conditions, within 10 seconds at 7.2x set current. The magnetic short-circuit release handles faults above that threshold. Rated impulse withstand voltage 6 kV, surge voltage resistance rated at that level, so it coordinates with standard distribution panel surge ratings. Power loss about 6 W total typical — negligible for enclosure heat calc but worth noting in a sealed cabinet.