Siemens 3RV6011-1KA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6011-1KA10 SIRIUS Motor Protection Circuit Breake

MPN3RV6011-1KA10

Siemens SIRIUS motor protection circuit breaker, 3RV6011-1KA10, size S00, 12.5 A rated operational current, Class 10 trip, thermal-magnetic overload and short-circuit release, 690 V, 50/60 Hz, screw-type terminals, snap-on 35 mm DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV6011-1KA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV6011-1KA10 — Electrical
ParameterValue
Rated operational current (Ie)12.5 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3

Protection & Tripping

3RV6011-1KA10 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Instantaneous short-circuit trip current163 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes

Connections

3RV6011-1KA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)

Mechanical

3RV6011-1KA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV6011-1KA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV6011-1KA10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens SIRIUS 3RV6011-1KA10 is a motor protection circuit breaker in the compact S00 frame size, rated 12.5 A operational current at AC-3 duty (400 V). The Class 10 trip characteristic means it will disconnect before the motor windings exceed their thermal limit during a locked-rotor event — the standard for standard-start induction motors driving pumps, fans, and conveyors. Thermal overload release handles sustained overcurrent; magnetic short-circuit trip clears faults instantly.

Snap-on mounting onto 35 mm DIN rail per EN 60715, in any orientation. The 45 mm width and 96 mm depth fit standard distribution panels with room for side-by-side grouping — 30 mm clearance needed to the side, 50 mm above and below. Screw-type terminals accept 2x (0.75 to 2.5 mm²) solid/stranded or 2x 4 mm²; torque to 0.8–1.2 N·m.

Rated for 50/60 Hz, 690 V max (AC-3). Power loss 7 W typical. Surge voltage resistance 6 kV. Shock rated 25 g / 11 ms per IEC 60068-2-27. Operating temperature -20 to +60 °C. Installation altitude up to 2000 m. Relative humidity 10–95 %. RoHS compliance date 05/01/2012.

Frequently asked questions

Where can I buy 3RV6011-1KA10 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figure is published here.

What is the closest functional alternative to 3RV6011-1KA10?

The 3RV6011-0CA10 is a lower-current sibling in the same S00 frame and Class 10 trip family. The 1KA10 carries a 12.5 A rating versus the 0CA10's lower amp setting — verify your motor FLA before substituting. Both share the same DIN footprint, terminal style, and thermal-magnetic design.

What compliance documentation does Siemens provide for 3RV6011-1KA10?

RoHS compliance is documented with a substance prohibition date of 05/01/2012. The part is designed to meet applicable IEC and UL standards for motor protection circuit breakers.

MPN
3RV6011-1KA10