Specifications

3RV6021-4BA15 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV6021-4BA15 — Electrical
ParameterValue
Rated operational current (Ie)20 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6021-4BA15 — Protection & Tripping
ParameterValue
Overload release setting range13 ... 20 A
Instantaneous short-circuit trip current260 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6021-4BA15 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV6021-4BA15 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6021-4BA15 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6021-4BA15 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

The Siemens 3RV6021-4BA15 is a SIRIUS motor protection circuit breaker, size S0, rated for 20 A operational current at 690 V AC-3. The magnetic short-circuit release handles fault clearing independently. Clearance requirements: 50 mm upwards and downwards, 30 mm at the sides, zero forwards or backwards. Screw-type terminals on both main and auxiliary circuits accept 2x (0.5…1.5 mm²) solid/stranded or 2x (0.75…2.5 mm²) with ferrules; AWG equivalents 2x (16…12) and 2x (14…8) for main contacts.

Rated operational current of 20 A at AC-3 governs motor sizing — pair this breaker with a motor whose full-load current does not exceed 20 A. The 690 V rated insulation voltage and 6 kV surge voltage resistance cover industrial transient environments. The magnetic short-circuit trip responds instantaneously to fault currents, providing Type 2 coordination with upstream contactors when properly selected. Typical power loss of 8 W total — relevant for thermal management in densely populated enclosures. Operating temperature range -20 to +60 °C with 10-95% relative humidity; storage range -50 to +80 °C. Shock resistance 25g / 11 ms per IEC 60068-2-27.

Integration & Compliance

The 3-pole design (3 main poles) with transverse auxiliary switch configuration allows integration of early-warning or trip-indication contacts into the control circuit. Screw terminals with tightening torque 2…2.5 N·m for main contacts. Substance prohibitance date of 05/01/2012 aligns with RoHS and REACH compliance timelines. The IEC ratings (surge voltage, shock, humidity) indicate design for international standards compliance.

Frequently asked questions

What is the 3RV6021-4BA15 used for?

It is a motor protection circuit breaker for three-phase induction motors up to 20 A full-load current. The Trip Class 10 overload release protects against sustained overloads and locked rotor conditions, while the magnetic short-circuit trip clears fault currents. It is typically mounted on DIN rail in motor control centers or individual motor starter enclosures.

What are the key dimensions for panel layout?

Width 45 mm, depth 96 mm, height 97 mm. Clearance: 50 mm above and below, 30 mm at sides, zero front/back. Mounts on 35 mm DIN rail per DIN EN 60715 in any position.

Does the 3RV6021-4BA15 drop into a panel specified for the 3RV6021-4DA10?

The 3RV6021-4BA15 and 3RV6021-4DA10 share the same S0 frame size, DIN rail mounting, and screw terminal layout — they are mechanically interchangeable in the same panel cutout and busbar arrangement. The difference is in the overload setting range: the 4BA15 is set for 20 A, while the 4DA10 covers a different current range. Verify the motor FLA matches the breaker's setting range before substituting.