Skip to main content
Siemens 3RV6021-4DA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6021-4DA10 SIRIUS Motor Protection Circuit Breake

MPN3RV6021-4DA10

Siemens SIRIUS 3RV6021-4DA10 motor protection circuit breaker, 25 A rated operational current, Class 10 trip, 690 V AC-3, size S0, screw terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6021-4DA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV6021-4DA10 — Electrical
ParameterValue
Rated operational current (Ie)25 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6021-4DA10 — Protection & Tripping
ParameterValue
Overload release setting range18 ... 25 A
Instantaneous short-circuit trip current325 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6021-4DA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
Conductor range, AWG (main contacts)2x (16 ... 12), 2x (14 ... 8)
3RV6021-4DA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6021-4DA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6021-4DA10 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

Motor protection circuit breaker, 25 A, Class 10

The thermal-magnetic overload release is Class 10. Size S0 frame, three-pole, with screw-type terminals accepting 2×(1–2.5 mm²) solid/stranded or 2×(2.5–10 mm²) for the main circuit.

Duty cycle and thermal behaviour

Rated for 15 operations per hour at AC-3 duty. Total power loss is 8 W typical. Shock resistance tested at 25 g / 11 ms per IEC 60068-2-27, and surge voltage withstand is 6 kV — both figures confirm the breaker holds its settings and doesn't nuisance-trip under mechanical or electrical transients common in industrial refrigeration compressor starts.

Frequently asked questions

What are the key ratings for the 3RV6021-4DA10?

Rated operational current 25 A in AC-3 duty, 690 V maximum, Class 10 thermal trip, size S0 frame, 45 mm wide, 96 mm deep.

Will the 3RV6021-4DA10 drop into a panel designed for a 3RV1011-1HA10?

Both are size S0 motor protection breakers on 35 mm DIN rail, so the footprint and mounting are compatible. However, the 3RV6021-4DA10 is rated 25 A while the 3RV1011-1HA10 covers a different current range — verify the motor full-load current and trip class match before substituting.

MPN
3RV6021-4DA10