Motor protection circuit breaker for 36 A AC-3 duty
It carries a rated operational current of 36 A at AC-3 400 V and a Trip Class 10 characteristic, meaning it will trip within 10 seconds at 7.2× the set current — standard for protecting standard induction motors during start-up. The breaker is rated for a maximum voltage of 690 V and operates at 50/60 Hz.
The S0 frame occupies 45 mm width, 97 mm height, and 96 mm depth. Clearance requirements: 70 mm upward and downward, 30 mm at the sides, 0 mm forward and backward. Screw-type terminals on the main current circuit accept 2×(1…2.5 mm²) solid/stranded or 2×(2.5…10 mm²) solid, with a tightening torque of 2…2.5 N·m. Connectors arranged top and bottom.
Operating temperature range -20 to +40 °C; transport/storage -50 to +80 °C. Relative humidity during operation 10 to 95 %. Installation altitude up to 2000 m. Shock resistance 25 g / 11 ms per IEC 60068-2-27. RoHS compliance date 05/01/2012. Surge voltage resistance rated at 6 kV.