Skip to main content
Siemens 3RV6311-0FC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6311-0FC10 SIRIUS Circuit Breaker, 0.5 A, S00 Fra

MPN3RV6311-0FC10

Siemens SIRIUS circuit breaker for starter combinations, 3RV6311-0FC10, S00 frame, 3-pole, 0.5 A rated operational current at AC-3/400 V, screw-type terminals, 35 mm DIN rail snap-on mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6311-0FC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6311-0FC10 — Electrical
ParameterValue
Rated operational current (Ie)0.5 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6311-0FC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current6.5 A
Short-circuit trip typemagnetic
Short-circuit protectionYes
3RV6311-0FC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)
3RV6311-0FC10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV6311-0FC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6311-0FC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

Instantaneous short-circuit trip responds at 6.5 A. Insulation voltage is 690 V at pollution degree 3; surge voltage withstand is 6 kV.

The S00 frame size gives a footprint of 45 mm wide, 97 mm tall, and 96 mm deep. That 96 mm depth means it sits flush with the backplane on a standard 100 mm-deep enclosure; if you are retrofitting into an existing panel that was laid out for the physically identical S00 frame (like the 3RV6011 series), the footprint and rail clip are the same — no rewiring of the bus bars needed provided the terminal arrangement is top-and-bottom as listed.

Frequently asked questions

Will 3RV6311-0FC10 drop into a panel designed for 3RV6011-0CA10?

Yes, provided the panel uses a 35 mm DIN rail per DIN EN 60715. Both parts share the S00 frame footprint and the same screw-and-snap-on mounting method. The terminal arrangement is top and bottom, so the bus-bar layout should be identical.

MPN