Siemens 3RV6311-1AC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6311-1AC10 SIRIUS Circuit Breaker, 1.6 A, 690 V,

MPN3RV6311-1AC10

Siemens SIRIUS circuit breaker, 3RV6311-1AC10, size S00, 1.6 A rated operational current at AC-3, 690 V, screw and snap-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6311-1AC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6311-1AC10 — Electrical
ParameterValue
Rated operational current (Ie)1.6 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6311-1AC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current21 A
Short-circuit trip typemagnetic
Short-circuit protectionYes
3RV6311-1AC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)
3RV6311-1AC10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV6311-1AC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6311-1AC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

Rated at 1.6 A operational current in AC-3 duty (switching motor loads up to that current at 400 V), it uses a magnetic short-circuit trip that responds at 21 A, so it clears a fault before the contactor welds.

At 45 mm wide, 97 mm tall, and 96 mm deep, it fits the standard S00 footprint; clearance of 50 mm above and below, 30 mm to the sides keeps airflow and wiring access clean.

Electrical Ratings and Environment

Rated for 690 V insulation voltage (pollution degree 3) and 6 kV surge withstand, it handles standard industrial supply voltages. Operating temperature spans -20 to +60 °C, storage from -50 to +80 °C, with 10–95 % relative humidity. Shock rated at 25 g / 11 ms per IEC 60068-2-27 — tough enough for machine-mounted applications. Total power loss is 6 W typical.

Substance prohibitance (RoHS-compliant) dated May 1, 2012. The SIRIUS series carries UL, CSA, and IEC certifications standard for the line — compliance documentation (declarations, CE marking) is available with the product.

Frequently asked questions

What are the key ratings of 3RV6311-1AC10?

Rated operational current 1.6 A at AC-3 (400 V), rated insulation voltage 690 V, magnetic short-circuit trip at 21 A, size S00, 3 poles, screw terminals.

Where can I buy 3RV6311-1AC10?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance documentation does 3RV6311-1AC10 carry?

RoHS compliance dated May 1, 2012. The SIRIUS series typically includes UL, CSA, and IEC certifications; declarations and CE marking are provided with the product.

MPN