What this breaker does in a motor branch
Rated 12.5 A at AC-3 duty (400 V), it handles the locked-rotor inrush of a motor up to that current class, then trips magnetically at 163 A for a hard fault. The 690 V rated insulation voltage with pollution degree 3 gives it headroom on 400 V line-to-line systems common in European and Asian panels.
Width 45 mm, depth 96 mm, height 97 mm. Screw terminals accept 2x (0.75 to 2.5 mm²) solid/stranded. Torque 0.8–1.2 N·m. Operating -20 to +60 °C.
Substance prohibition (RoHS) compliance date 05/01/2012. Shock resistance 25g / 11 ms per IEC 60068-2-27. Surge voltage resistance 6 kV. Relative humidity 10–95 % during operation. The SIRIUS series carries UL, CSA, CE, and IEC certifications standard for the brand — documentation available on request.