Siemens 3RV6321-4EC10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6321-4EC10 SIRIUS Circuit Breaker, 32 A AC-3, 690

MPN3RV6321-4EC10

Siemens SIRIUS circuit breaker for starter combinations, size S0, 3-pole, 32 A AC-3 at 400 V, 690 V rated, magnetic short-circuit trip 400 A, screw terminals, snap-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6321-4EC10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS0
3RV6321-4EC10 — Electrical
ParameterValue
Rated operational current (Ie)32 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6321-4EC10 — Protection & Tripping
ParameterValue
Instantaneous short-circuit trip current400 A
Short-circuit trip typemagnetic
Short-circuit protectionYes
3RV6321-4EC10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
Conductor cross-section, finely stranded with ferrule2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
Conductor range, AWG (main contacts)2x (16 ... 12), 2x (14 ... 8)
3RV6321-4EC10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV6321-4EC10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6321-4EC10 — Specifications
ParameterValue
Design Of The Productfor starter combinations

Product details

What this SIRIUS breaker does in a motor branch

The magnetic short-circuit trip responds at 400 A, so it clears a bolted fault fast enough to protect the contactor downstream without welding the main contacts. The S0 frame size keeps the width at 45 mm — three of these fit in a standard 145 mm wide DIN-rail section, which matters for panel density. Depth is 96 mm, so it clears a 100 mm deep enclosure but check gland-plate clearance if the backplane is tight.

Clearance and mounting — what fits where

The 3RV6321-4EC10 needs 50 mm clearance above and below for air circulation and arc-chamber venting, 30 mm at the sides. Zero clearance forwards and backwards — it can sit flush against a backplate or enclosure door. That 50 mm vertical gap is non-negotiable if you want the breaker to trip free under fault without ionized gas tracking to adjacent metalwork. Terminal capacity: screw-type terminals accept 2 x (1 to 2.5 mm²) solid/stranded or 2 x (2.5 to 10 mm²), with a tightening torque of 2 to 2.5 N·m. For finely stranded wire with ferrule, it takes 2 x (1 to 2.5 mm²), 2 x (2.5 to 6 mm²), or a single 10 mm². That covers most panel-building wire sizes up to the 32 A rating without needing adapter lugs.

Lifecycle and compliance — what the nameplate tells procurement

Relative humidity 10 to 95 % non-condensing. Shock resistance 25 g / 11 ms per IEC 60068-2-27 — survives a forklift bump into the panel or a nearby press hit.

Frequently asked questions

Where can I buy the 3RV6321-4EC10 and what is the lead time?

We source and quote the 3RV6321-4EC10 to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network. Submit an RFQ for a firm price and lead time.

Will the 3RV6321-4EC10 drop into a panel specified around the 3RV6021-4DA10?

Mechanically yes — both mount on 35 mm DIN rail with screw terminals in the S0 frame size. Electrically, verify the AC-3 current rating and the instantaneous short-circuit trip point match your motor protection scheme. The 3RV6321-4EC10 is rated 32 A AC-3 with a 400 A magnetic trip; confirm these align with the original specification.

What compliance documentation does Siemens provide for the 3RV6321-4EC10?

The part carries a substance prohibitance date of 05/01/2012, aligning with EU RoHS recast requirements. It is designed to IEC/EN 60947-2 and 60947-4-1 standards for motor circuit protectors. Insulation voltage 690 V at pollution degree 3, surge voltage resistance 6 kV. Standard Siemens documentation includes the declaration of conformity and the datasheet.