Skip to main content
Siemens 3RV6411-0BA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6411-0BA10 SIRIUS Circuit Breaker, 0.2 A, Class 1

MPN3RV6411-0BA10

Siemens SIRIUS circuit breaker, 3RV6411-0BA10, for transformer protection, 0.2 A rated current, Class 10 trip, 690 V, 3-pole, size S00, screw-type terminals, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV6411-0BA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV6411-0BA10 — Electrical
ParameterValue
Rated operational current (Ie)0.2 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
3RV6411-0BA10 — Protection & Tripping
ParameterValue
Overload release setting range0.14 ... 0.2 A
Instantaneous short-circuit trip current4.2 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
3RV6411-0BA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor range, AWG (main contacts)2x (18 to 12), 2x (20 to 16)
3RV6411-0BA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Mounting positionany
3RV6411-0BA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV6411-0BA10 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

Rated for 690 V at 50/60 Hz, this 3-pole breaker uses a thermal overload release and a magnetic short-circuit trip.

The S00 frame size keeps the footprint compact: 45 mm wide, 97 mm tall, 96 mm deep. That 96 mm depth means it sits flush with typical S00 contactors in a motor-starter stack. Screw-type terminals on top and bottom accept 2×(0.75–2.5 mm²) solid/stranded or 2×4 mm², with a tightening torque of 0.8–1.2 N·m. AWG equivalents: 2×(18–12) solid, 2×(20–16) stranded. That covers most control-circuit wiring; for larger transformer secondaries, you'd step up to the S0 frame.

Compliance documentation is in order: RoHS compliance date of May 1, 2012 (per EU Directive 2011/65/EU), and the part carries the usual SIRIUS approvals (UL, CSA, CE) for panel builders shipping into North America or Europe.

Frequently asked questions

Will 3RV6411-0BA10 drop into a panel that was specified around 3RV6011-0CA10 without rewiring?

Physically, yes — both are S00 size, 45 mm wide, mount on the same 35 mm DIN rail, and use the same screw-terminal layout. No rewiring of the DIN rail or terminal positions is needed. But the overload curve is different: the 3RV6411-0BA10 is for transformer primary protection, not motor protection. If the original panel was a motor starter, the 3RV6411-0BA10 will trip incorrectly on motor inrush.

MPN
3RV6411-0BA10