Skip to main content
Siemens 3RV6411-1KA10 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV6411-1KA10 SIRIUS Circuit Breaker, 12.5 A, Class

MPN3RV6411-1KA10

Siemens SIRIUS circuit breaker, 3RV6411-1KA10, for transformer protection, 3-pole, rated 12.5 A, Class 10, 690 V AC-3, screw terminals, size S00, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3RV6411-1KA10 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00

Electrical

3RV6411-1KA10 — Electrical
ParameterValue
Rated operational current (Ie)12.5 A
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3

Protection & Tripping

3RV6411-1KA10 — Protection & Tripping
ParameterValue
Overload release setting range9 ... 12.5 A
Instantaneous short-circuit trip current260 A
Trip classCLASS 10
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes

Connections

3RV6411-1KA10 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)

Mechanical

3RV6411-1KA10 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth96 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany

Environmental

3RV6411-1KA10 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m

Specifications

3RV6411-1KA10 — Specifications
ParameterValue
Design Of The Productfor transformer protection

Product details

The Siemens 3RV6411-1KA10 is a SIRIUS circuit breaker designed specifically for transformer protection, with a rated operational current of 12.5 A in AC-3 duty and a Class 10 trip characteristic. That Class 10 means it trips fast enough to protect a transformer winding against sustained overload without nuisance tripping on inrush — a common headache when a standard motor-protective breaker is used instead. Rated for 690 V AC-3 and 50/60 Hz, it handles the primary-side switching of small to medium transformers in control panels and distribution boards.

Mounting and integration

Mounts via screw and snap-on onto 35 mm DIN rail per DIN EN 60715, in any position. The S00 frame size keeps the width to 45 mm, depth 96 mm, height 97 mm — fits a standard 45 mm DIN slot. Clearance: 50 mm above and below, 30 mm at the sides, nothing needed front or back. Screw-type terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm²; torque to 0.8 to 1.2 N·m.

Environmental and mechanical ratings

Operating temperature -20 to +60 °C, transport/storage -50 to +80 °C. Relative humidity 10 to 95 %. Shock resistant to 25 g / 11 ms per IEC 60068-2-27. Installation altitude up to 2000 m above sea level. Total power loss 7 W typical.

Frequently asked questions

What is 3RV6411-1KA10 used for?

It is a circuit breaker designed for transformer protection, rated 12.5 A, Class 10 trip, 690 V AC-3, 3-pole, with thermal overload and magnetic short-circuit releases.

Where can I buy 3RV6411-1KA10?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does this part have?

RoHS compliance date is 05/01/2012. The part also carries the SIRIUS brand and is designed per IEC/EN standards.

MPN