It carries a 16 A rated operational current and a Class 10 trip characteristic, meaning it allows the inrush of a transformer while still tripping fast enough on a hard fault.
Screw-type terminals on top and bottom accept up to 10 mm² solid or 6 mm² finely stranded with ferrules, or 2x 10 mm² solid. Torque to 2–2.5 N·m. Depth is 96 mm, width 45 mm, height 97 mm — fits standard panel layouts.