Skip to main content
Siemens 3RW4024-1BB04 — Soft Starters

Siemens 3RW4024-1BB04 SIRIUS Soft Starter, 12.5 A, 24 V, Siz

MPN3RW4024-1BB04
Active

Siemens SIRIUS soft starter, 3RW4024-1BB04, 12.5 A rated current at 40 °C, 24 V AC/DC control supply, Size S0, screw-type terminals, integrated bypass contact system.

$371.18Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW4024-1BB04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW4024-1BB04 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C12.5A
Rated operational current at 50 °C11A
Rated operational current at 60 °C10A
Rated insulation voltage600V
Minimum settable current (% of Ie)20%
3RW4024-1BB04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24V
Rated voltage at 60 Hz24V
Main circuit terminal typescrew-type terminals
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
3RW4024-1BB04 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionNo
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW4024-1BB04 — Mechanical
ParameterValue
Height125mm
Width45mm
Depth155mm
Mounting positionWith additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t
Fastening methodscrew and snap-on mounting
Mounting clearance, top60mm
Mounting clearance, bottom40mm
Mounting clearance, side15mm
3RW4024-1BB04 — Environmental
ParameterValue
Operating temperature range-25 ... +60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

Rated at 12.5 A at 40 °C, the 3RW4024-1BB04 derates to 11 A at 50 °C and 10 A at 60 °C. The derating threshold starts at 40 °C, so any panel ambient above that requires a downward adjustment in the motor FLA the starter can handle. For a 400 V motor, that 12.5 A at 40 °C corresponds to roughly 5.5 kW (standard 4-pole induction motor); at 60 °C the same motor would need a larger frame.

Control supply and wiring

Control supply is 24 V AC/DC, 50/60 Hz. Main power and control circuits terminate on screw-type terminals. For the main circuit, the terminal accepts 2x (0.5... 2.5 mm²) solid or stranded; auxiliary and control circuit terminals accept 2x (20... 14) AWG. A front clamping point is available for 1x 8 or 2x (16... 10) AWG. Maximum motor cable length is 300 m — keep that in mind for remote motor installations; longer runs may require output reactors.

Mounts on DIN rail or directly with screws (screw and snap-on mounting). Dimensions: 45 mm wide, 125 mm high, 155 mm deep — fits a standard S0 footprint. Clearance requirements: 60 mm above, 40 mm below, 15 mm to the side. Mounting position is flexible with restrictions: with an additional fan, the unit can be mounted vertically with ±90° rotation and ±22.5° tilt front/back; without a fan, only ±10° rotation and ±10° tilt.

Protection and adjustability

Built-in motor overload protection and intrinsic device protection are standard. The current limitation is adjustable, and the minimum load is 20 % of the rated current — so it won't properly soft-start a motor drawing less than about 2.5 A. An external reset input allows remote fault reset. A red LED indicates fault signals.

Frequently asked questions

Where can I buy 3RW4024-1BB04 and how do I get a price?

The 3RW4024-1BB04 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of the 3RW4024-1BB04?

Rated 12.5 A at 40 °C (derates to 11 A at 50 °C, 10 A at 60 °C), control supply 24 V AC/DC, insulation voltage 600 V, operating frequency 50/60 Hz, and integrated bypass contact.

What are the mounting dimensions and clearances for 3RW4024-1BB04?

Width 45 mm, height 125 mm, depth 155 mm. Required clearances: 60 mm above, 40 mm below, 15 mm to the side. Mounts via screw or snap-on on DIN rail.

What compliance documentation does this brand provide for 3RW4024-1BB04?

The device is designed to IEC 60947-4-2 (pollution degree 3) and carries the SIRIUS brand. Specific RoHS, REACH, UL, and IEC declarations are available from the manufacturer upon request.

MPN
3RW4024-1BB04