Siemens 3RW4026-2BB15 Soft Starter, 25 A, Size S0

MPN3RW4026-2BB15
Active

Siemens SIRIUS 3RW4026-2BB15 soft starter, Size S0, 25 A at 40 °C, 110-230 VDC control, spring-loaded terminals, integrated bypass.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW4026-2BB15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW4026-2BB15 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C25A
Rated operational current at 50 °C23A
Rated operational current at 60 °C21A
Rated insulation voltage600V
Minimum settable current (% of Ie)20%
3RW4026-2BB15 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Main circuit terminal typespring-loaded terminals
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
3RW4026-2BB15 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionNo
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW4026-2BB15 — Mechanical
ParameterValue
Height150mm
Width45mm
Depth155mm
Mounting positionWith additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t
Fastening methodscrew and snap-on mounting
Mounting clearance, top60mm
Mounting clearance, bottom40mm
Mounting clearance, side15mm
3RW4026-2BB15 — Environmental
ParameterValue
Operating temperature range-25 ... +60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

What this soft starter delivers

The Siemens 3RW4026-2BB15 is a SIRIUS soft starter in the Size S0 frame, rated 25 A at 40 °C. That 25 A figure is the continuous motor current it can handle in standard ambient — at 50 °C it derates to 23 A, and at 60 °C to 21 A, so if your panel runs hot you size off the derated number, not the headline. It carries an integrated bypass contact system, meaning once the motor is up to speed the thyristors are shorted out — no continuous heat dissipation from the semiconductors, which keeps the enclosure cooler and extends component life. Control supply is 110-230 VDC, a single DC rail that covers most industrial control voltages without needing a separate transformer tap.

Depth is 155 mm, so account for that when spacing the backplane. Main current circuit uses spring-loaded terminals; auxiliary and control circuits also use spring-loaded terminals. Accepts 2x (0.25... 2.5 mm²) solid or stranded — strip length is whatever the terminal spec calls for, but 8 mm is typical for this class. Clearance: 60 mm upwards, 40 mm downwards, 15 mm at the sides — those are the minimum air gaps for heat dissipation, not suggestions.

Protection and control features

Built-in motor overload protection and intrinsic device protection — the soft starter monitors its own temperature and the motor current. Adjustable current limitation lets you set the starting torque profile without external hardware. External reset is supported — useful if the starter is inside a locked panel and you want a remote reset button on the door. Minimum load is 20 % of the rated current; below that the internal current sensing may not trip reliably. Rated insulation voltage is 600 V, and the pollution degree is 3 per IEC 60947-4-2 — that's conductive pollution typical of industrial environments, so no derating needed for dusty or mildly humid panels.

Frequently asked questions

Does the 3RW4026-2BB15 require an external reset?

It supports an external reset, but it is not required — the soft starter can be reset locally. The external reset option is useful for remote panel installations.

MPN
3RW4026-2BB15