Siemens 3RW4026-2TB04 — Soft Starters

Siemens 3RW4026-2TB04 SIRIUS Soft Starter, 25 A, Size S0

MPN3RW4026-2TB04
Active

Siemens SIRIUS 3RW4026-2TB04 soft starter, Size S0, 25 A at 40 °C, 50/60 Hz, 600 V insulation, spring-loaded terminals, integrated bypass, screw and snap-on mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW4026-2TB04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW4026-2TB04 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C25A
Rated operational current at 50 °C23A
Rated operational current at 60 °C21A
Rated insulation voltage600V
Minimum settable current (% of Ie)20%
3RW4026-2TB04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24V
Rated voltage at 60 Hz24V
Main circuit terminal typespring-loaded terminals
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
3RW4026-2TB04 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionNo
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW4026-2TB04 — Mechanical
ParameterValue
Height150mm
Width45mm
Depth155mm
Mounting positionWith additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t
Fastening methodscrew and snap-on mounting
Mounting clearance, top60mm
Mounting clearance, bottom40mm
Mounting clearance, side15mm
3RW4026-2TB04 — Environmental
ParameterValue
Operating temperature range-25 ... +60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

The 3RW4026-2TB04: Spring-loaded terminals on both the main current circuit and the auxiliary/control circuit mean no screw torque to check; strip and insert solid or ferruled stranded wire up to 2.5 mm². Clearance: 60 mm above, 40 mm below, 15 mm at the side for airflow — the derating curve starts at 40 °C ambient, so pack the cabinet with that in mind.

Current derating and the integrated bypass — what the 25 A rating actually means

An integrated bypass contact system closes after start-up, shunting the thyristors and cutting heat dissipation in the cabinet during run — this is what lets the S0 frame handle 25 A continuous without a fan at 40 °C. Adjustable current limitation lets you set the start current between 20 % and 100 % of the soft starter's rated current, matching the motor's inrush characteristic without oversizing the starter.

Active production — no end-of-life watch needed

Motor overload protection and intrinsic device protection are built in — no separate overload relay needed for most applications, which simplifies the BOM and panel wiring. Insulation voltage rated 600 V, pollution degree 3 per IEC 60947-4-2 — suitable for industrial environments with conductive dust or condensation.

Mounting position and cable length constraints

With the optional fan, the unit can be mounted on a vertical surface and rotated ±90° or tilted ±22.5° front-to-back; without the fan, rotation is limited to ±10°. Maximum motor cable length is 300 m — beyond that, capacitive charging current from the cable can interfere with the thyristor firing and cause nuisance trips. External reset input and a red LED fault signal give the technician a clear indication and remote reset capability without opening the panel door.

Frequently asked questions

What is the 3RW4026-2TB04's current rating at different temperatures?

The integrated bypass contact system shunts the thyristors during run, reducing heat load in the cabinet.

Does the 3RW4026-2TB04 have an integrated bypass?

Yes — an integrated bypass contact system closes after the motor reaches speed, taking the thyristors out of circuit and eliminating their continuous power dissipation.

What termination type does the 3RW4026-2TB04 use?

Spring-loaded terminals on both the main current circuit and the auxiliary/control circuit.

What is the 3RW4026-2TB04's mounting position flexibility?

With the optional fan, mount on a vertical surface with ±90° rotation or ±22.5° tilt front-to-back. Without the fan, rotation is limited to ±10°.

MPN
3RW4026-2TB04