It delivers adjustable current limitation and built-in motor overload protection, with an external reset input for remote fault recovery. The control supply accepts 110 … 230 V DC, and the operating frequency is 50 … 60 Hz. Rated current derates with ambient: 73 A at 50 °C, 66 A at 60 °C. The 20% minimum load setting prevents nuisance tripping on lightly loaded motors.
Fastens via screw and snap-on mounting. Dimensions: 70 mm wide, 170 mm high, 190 mm deep. Clearance requirements: 60 mm above, 40 mm below, 30 mm at the sides. With an additional fan, the mounting surface can be vertical and rotated ±90° or tilted ±22.5° front/back; without a fan, rotation and tilt are limited to ±10°. Main circuit uses screw-type terminals. Solid wire: 2x (0.5 … 2.5 mm²). Stranded: 2x (10 … 70 mm²). Finely stranded: 2x (10 … 50 mm²). Auxiliary contacts accept 2x (20 … 14 AWG). Maximum wire length to motor: 300 m.