SIRIUS S3 soft starter — 106 A at 40 °C, adjustable current limit
The 3RW4047-1BB15: Control supply accepts 110-230 V DC, and the unit operates on 50-60 Hz mains. The adjustable current limitation (20% minimum load) and integrated motor overload protection let you set the ramp and trip threshold without an external relay. Mounting is screw or snap-on (DIN rail), with the fastening method allowing vertical surface rotation up to ±90° when an additional fan is fitted. Without the fan, rotation is limited to ±10° — plan the panel layout accordingly.
Terminal sizing and wire preparation
The back and front clamping points both handle 2x (10-1/0 AWG). Solid wire for aux contacts is 2x (0.5-2.5 mm²). Maximum wire length to the motor is 300 m — sufficient for most in-plant runs.
Active production — sourcing against your BOM