106 A at 40 °C — the number that decides the motor
The 3RW4047-2TB04: Thyristor-based output stages handle the inrush without mechanical contact wear. Adjustable current limitation and built-in motor overload protection mean you can set the ramp ceiling and let the soft starter guard the winding during start.
Mounting and wiring — fits a standard panel slot
The S3 frame measures 170 mm high by 70 mm wide by 190 mm deep. Screw and snap-on mounting to DIN rail — no bracket kit needed. Clearance: 60 mm above, 40 mm below, 30 mm at the sides. Auxiliary terminals take 24 to 14 AWG. Screw-type termination throughout — torque to spec, no special crimp tooling required.
Operating envelope and compliance
Runs on 50 or 60 Hz supply, 24 V control voltage at both frequencies. Insulation rated 600 V, pollution degree 3 per IEC 60947-4-2 — suitable for industrial environments with conductive dust or condensation. Mounting position is flexible: vertical surface with up to +/-90° rotation when using the optional fan, or +/-10° rotation without it.