134 A at 40 °C — current derating drives the panel sizing
The 3RW4055-6BB34: Insulation voltage rated 600 V, operating frequency 50/60 Hz. Pollution degree 3 per IEC 60947-4-2 means the soft starter is designed for the conductive dust and humidity typical of industrial control panels, not clean-room or office environments.
Wiring and mounting — size S6, busbar or lug
For auxiliary contacts, 2x (20 … 14) AWG. Mounting position allows vertical surface with +/-90° rotation and +/-22.5° tilt (with additional fan) or +/-10° rotation without fan. Dimensions: 250 mm depth, 120 mm width, 198 mm height. Screw fixing.
Adjustable current limitation and motor protection
Built-in motor overload protection and intrinsic device protection — the soft starter monitors the motor current and trips on overload without an external relay. Adjustable current limitation lets you set the starting current between 20% and the rated value. External reset input allows remote fault reset, useful in unattended or remote installations. Maximum motor cable length 300 m.