Siemens 3RW4426-3BC36 — Soft Starters

Siemens 3RW4426-3BC36 SIRIUS Soft Starter, 133A

MPN3RW4426-3BC36

Siemens SIRIUS 3RW4426-3BC36 soft starter, 133A at 40°C, 115V AC control voltage, inside-delta circuit, integrated bypass contact system, 170 x 192 x 270 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW4426-3BC36 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW4426-3BC36 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C133A
Rated operational current at 50 °C118A
Rated operational current at 60 °C102A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%

Control & Connection

3RW4426-3BC36 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz115V
Rated voltage at 60 Hz115V
Main circuit terminal typebox terminal
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%

Protection & Features

3RW4426-3BC36 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW4426-3BC36 — Mechanical
ParameterValue
Height192mm
Width170mm
Depth270mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm

Environmental

3RW4426-3BC36 — Environmental
ParameterValue
Operating temperature range60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

133 A at 40 °C — what that means for the motor line

The 3RW4426-3BC36 is a SIRIUS soft starter rated 133 A at 40 °C in standard duty. That current rating governs the maximum motor full-load amps it can ramp up and protect — size it for a motor drawing up to 133 A FLA and the thyristor stack handles the inrush without bypassing until the motor is up to speed. The integrated bypass contact system takes over after start, shunting the thyristors so they cool between starts — that's what lets this unit handle repeated starts without oversized heatsinks.

Inside-delta wiring and control voltage

This soft starter supports inside-delta circuit configuration, which means the thyristors sit inside the motor delta winding rather than in the supply lines. That cuts the phase current the thyristors see by about 58%, effectively letting a 133 A unit control a motor with a higher FLA than its line rating would suggest — a common trick for larger motors where a smaller soft starter saves panel space and cost. The auxiliary and control circuit uses spring-loaded terminals; the main current circuit uses box terminals sized for 2x (4 … 50 mm²) stranded.

Mounting, clearances, and environmental limits

Mounting is screw-fixing on a vertical surface, rotatable ±90° and tiltable ±22.5° front-to-back. Keep 100 mm clearance above and 75 mm below for airflow. The 270 mm depth fits a standard enclosure with room for wiring.

Frequently asked questions

What is the replacement for 3RW4426-3BC36?

Buyers need to know the preferred successor to avoid purchasing an obsolete unit and ensure long-term support.

Is 3RW4426-3BC36 obsolete?

Designers and maintenance planners must know lifecycle status to make informed design or repair decisions.

Where to buy 3RW4426-3BC36?

Sourcing buyers need immediate distributor options to fill BOM lines or urgent repairs.

What is the price of 3RW4426-3BC36?

Budgeting and cost comparison drive purchasing decisions and replacement evaluations.

What are the electrical specifications of 3RW4426-3BC36?

Design engineers must verify fit for motor voltage, current, and control voltage before integration.

Can 3RW4426-3BC36 be used in an inside-delta configuration?

This configuration changes current rating significantly (68A vs 118A) and affects motor sizing.

MPN