Siemens 3RW4426-3BC46 — Soft Starters

Siemens 3RW4426-3BC46 SIRIUS Soft Starter, 133 A, 230 V

MPN3RW4426-3BC46

Siemens SIRIUS 3RW4426-3BC46 soft starter, 133 A at 40 °C, 230 V, 50/60 Hz, 3-phase, integrated bypass, screw fixing.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW4426-3BC46 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW4426-3BC46 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C133A
Rated operational current at 50 °C118A
Rated operational current at 60 °C102A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%

Control & Connection

3RW4426-3BC46 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz230V
Rated voltage at 60 Hz230V
Main circuit terminal typebox terminal
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%

Protection & Features

3RW4426-3BC46 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW4426-3BC46 — Mechanical
ParameterValue
Height192mm
Width170mm
Depth270mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm

Environmental

3RW4426-3BC46 — Environmental
ParameterValue
Operating temperature range60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

Rated current and thermal derating

The 3RW4426-3BC46: This derating curve is the primary selection gate — a 40 °C panel environment buys the full 133 A, but a 50 °C enclosure drops available current by over 11 %. The 8 % minimum load setting means it handles lightly loaded motors without tripping on undercurrent.

Integrated bypass and inside-delta wiring

An integrated bypass contact system and thyristor stack mean the soft starter runs the motor through the SCRs only during start and stop; once at speed, the bypass closes and the SCRs cool. This reduces heat dissipation in the enclosure and extends thyristor life. The inside-delta circuit option allows wiring the soft starter in the motor delta loop, reducing the unit's current rating requirement by about 42 % compared to in-line connection — a common trick for larger motors where panel space is tight.

Mounting, clearances, and terminations

Screw fixing to a vertical mounting surface; the unit can be rotated ±90° or tilted ±22.5° front-to-back. Minimum clearance: 100 mm above, 75 mm below, 5 mm at the sides. The 270 mm depth and 170 mm width fit a standard 600 mm deep enclosure with room for gland plates.

Protection and control features

Motor overload protection and intrinsic device protection are built in — no separate overload relay needed for most applications. Adjustable current limitation lets you set the start current between the minimum load threshold and the unit's rated maximum. External reset supports remote restart after a fault. The display shows fault codes, which speeds troubleshooting on the line.

Frequently asked questions

What is the maximum motor cable length for 3RW4426-3BC46?

The maximum motor cable length is 500 m. This applies to the total run between the soft starter and the motor; longer runs increase voltage drop and may affect starting torque.

MPN