Skip to main content
Siemens 3RW4436-2BC34 — Soft Starters

Siemens 3RW4436-2BC34 SIRIUS Soft Starter, 281 A, 690 V

MPN3RW4436-2BC34

Siemens SIRIUS 3RW4436-2BC34 soft starter, 281 A at 40 °C, 690 V insulation voltage, 50/60 Hz, inside-delta circuit, screw fixing, 170 x 200 x 270 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW4436-2BC34 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW4436-2BC34 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C281A
Rated operational current at 50 °C251A
Rated operational current at 60 °C217A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%
3RW4436-2BC34 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz115V
Rated voltage at 60 Hz115V
Main circuit terminal typebusbar connection
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%
3RW4436-2BC34 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW4436-2BC34 — Mechanical
ParameterValue
Height200mm
Width170mm
Depth270mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm
3RW4436-2BC34 — Environmental
ParameterValue
Operating temperature range60°C

Product details

Rated current and thermal derating — what the numbers mean for your motor

The 3RW4436-2BC34: The soft starter is rated 281 A at 40 °C ambient. This is the full-load current it can handle continuously at that temperature. The derating temperature threshold is 40 °C — above that, you must reduce the load current or improve cabinet ventilation to stay within the device's thermal limits. The insulation voltage is rated 690 V, and the operating frequency covers 50 to 60 Hz. Inside-delta circuit configuration is supported, which reduces the current through the soft starter to 58% of the motor full-load current — useful for larger motors where the starter frame size can be downsized. Adjustable current limitation and motor overload protection are built in, along with intrinsic device protection (thyristor overtemperature, phase imbalance).

Mounting, wiring, and panel integration

Dimensions are 170 mm wide, 200 mm high, 270 mm deep. Fastening is by screw fixing to a vertical mounting surface, rotatable ±90° and tiltable ±22.5° front-to-back. This gives flexibility in cabinet layout — the unit can be mounted on a backplate or sidewall without special brackets. Main circuit connections accept stranded wire 25–120 mm² or busbar connection. Auxiliary control wiring uses solid wire 0.25–1.5 mm² (2x terminals). The main terminals also accept AWG 4–250 kcmil. Maximum motor cable length is 500 m — sufficient for most industrial installations without output reactors. Degree of pollution is 3 per IEC 60947-4-2, meaning the device is suitable for industrial environments with conductive pollution or dry non-conductive pollution that becomes conductive due to condensation. Clearance distances: 100 mm upwards, 75 mm downwards, 5 mm at the sides.

Protection and diagnostics

The soft starter includes a display for fault signals, showing the fault type directly on the unit — no need for a separate HMI or software to read error codes. External reset input allows remote fault clearing from a PLC or pushbutton panel. Minimum load is 8% of the rated current — the device can start very lightly loaded motors without instability. Storage temperature range is -25 to +80 °C, operating ambient up to 60 °C.

Frequently asked questions

What is the rated current of 3RW4436-2BC34 at different temperatures?

At 40 °C the continuous rated current is 281 A. The derating temperature threshold is 40 °C.

Does 3RW4436-2BC34 support inside-delta connection?

Yes, inside-delta circuit configuration is supported. This allows the soft starter to handle motor full-load current at 58% of the line current, enabling a smaller starter frame size for a given motor.

What compliance documentation does Siemens provide for 3RW4436-2BC34?

The device is designed to IEC 60947-4-2 (degree of pollution 3). Standard Siemens documentation includes the datasheet, operating instructions, and CE declaration of conformity. Specific RoHS/REACH status should be confirmed from the manufacturer's current compliance declarations.

MPN
3RW4436-2BC34