Siemens 3RW4454-6BC36 Soft Starter, 1,065 A, SIRIUS

MPN3RW4454-6BC36

Siemens SIRIUS 3RW4454-6BC36 soft starter, 1,065 A at 40°C, 690 V insulation voltage, integrated bypass contact system, inside-delta circuit capable, screw fixing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW4454-6BC36 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW4454-6BC36 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C1 065A
Rated operational current at 50 °C954A
Rated operational current at 60 °C847A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%
3RW4454-6BC36 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz115V
Rated voltage at 60 Hz115V
Main circuit terminal typebusbar connection
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%
3RW4454-6BC36 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW4454-6BC36 — Mechanical
ParameterValue
Height640mm
Width510mm
Depth290mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm
3RW4454-6BC36 — Environmental
ParameterValue
Operating temperature range60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

1,065 A at 40°C — the rating that governs the motor starting duty

The 3RW4454-6BC36 is rated 1,065 A at 40°C ambient. That is the base current for sizing the soft starter to the motor full-load amps — not the peak inrush, but the continuous current the thyristors and bypass contacts carry once the motor is up to speed. Derate to 954 A at 50°C and 847 A at 60°C. If the panel ambient runs above 40°C — common in a packed enclosure with drives and transformers — the usable current drops. The derating temperature is 40°C; above that, apply the curve. Insulation voltage is 690 V rated, operating frequency 50/60 Hz. The minimum load is 8% — it will start lightly loaded conveyors or pumps without the motor drawing enough current to keep the thyristors in conduction.

Integrated bypass — one less component to panel-build

The bypass contact system is built in. Once the motor reaches full speed, the thyristors are shorted by mechanical contacts, eliminating the continuous heat load of the semiconductors. No external bypass contactor to wire, size, or fail. Inside-delta circuit is supported. For a delta-connected motor, wiring the soft starter inside the delta legs reduces the line current by about 42% compared to the standard in-line connection. The unit handles the same motor kW at lower line amps — useful when the supply transformer or cable is the constraint. Motor overload protection is onboard, plus intrinsic device protection and adjustable current limitation. The display shows fault signals. External reset is available.

Panel fit — 640 x 510 x 290 mm, screw-fixed

Height 640 mm, width 510 mm, depth 290 mm. Fastening method is screw fixing — not DIN-rail snap-on at this frame size. The mounting position allows vertical surface with +/-90° rotation and +/-22.5° tilt front/back. Clearance: 100 mm upwards, 75 mm downwards, 5 mm at the sides. The side clearance is tight — adjacent devices or enclosure walls must respect that 5 mm for airflow and arc flash containment. Pollution degree 3 per IEC 60947-4-2 means it is rated for conductive dust environments typical of cement, woodworking, or foundry panels. Main current circuit connection is busbar. Power wiring: stranded 70–240 mm², finely stranded 50–240 mm², or AWG 2/0–500 kcmil. Maximum motor cable length is 500 m.

The 3RW4454-6BC36 is a SIRIUS-branded soft starter. It includes a motor brake output component and a display for fault signaling. Compliance documentation (RoHS, REACH, UL, IEC) is provided with the shipment per Siemens standard.

Frequently asked questions

What is the rated current of 3RW4454-6BC36 at different temperatures?

Rated 1,065 A at 40°C, derated to 954 A at 50°C, and 847 A at 60°C. The derating temperature threshold is 40°C.

Does 3RW4454-6BC36 include a built-in bypass contactor?

Yes, the integrated bypass contact system is standard. No external bypass contactor is needed, which saves panel space and wiring.