Skip to main content
Siemens 3RW4456-2BC34 — Soft Starters

Siemens 3RW4456-2BC34 SIRIUS Soft Starter, 1351 A at 40°C

MPN3RW4456-2BC34

Siemens SIRIUS 3RW4456-2BC34 soft starter, 1351 A at 40°C, 690 V insulation, 640×510×290 mm, screw fixing, integrated bypass contact system, inside-delta circuit.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW4456-2BC34 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW4456-2BC34 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C1 351A
Rated operational current at 50 °C1 200A
Rated operational current at 60 °C1 065A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%

Control & Connection

3RW4456-2BC34 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz115V
Rated voltage at 60 Hz115V
Main circuit terminal typebusbar connection
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%

Protection & Features

3RW4456-2BC34 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW4456-2BC34 — Mechanical
ParameterValue
Height640mm
Width510mm
Depth290mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm

Environmental

3RW4456-2BC34 — Environmental
ParameterValue
Operating temperature range60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

1351 A frame — what the derating curve means for your panel

The 3RW4456-2BC34 is rated 1351 A at 40°C, derating to 1200 A at 50°C and 1065 A at 60°C. In a non-conditioned enclosure hitting 50°C ambient, budget for 1200 A continuous — the 1351 A number is only valid at or below 40°C. For a 1351 A bypass contactor, that's a significant panel cost and space reduction. Inside-delta circuit capability reduces motor cable current to 58% of line current — for a 1351 A motor, the cable between soft starter and motor carries ~783 A instead of the full 1351 A, allowing smaller cable or longer runs.

Mounting and clearances — screw-fixed, not DIN-rail

Mounting position allows ±90° rotation and ±22.5° tilt, useful for tight cabinets or angled backplates. Clearance requirements: 100 mm above, 75 mm below, only 5 mm at the sides — the tight side clearance helps pack multiple units side-by-side. Main current circuit connection is busbar — expect flat copper bars, not cable lugs, in the panel layout. Auxiliary and control circuit terminals are spring-loaded, accepting solid 0.25-1.5 mm² or stranded 70-240 mm² for mains. For North American installs, main terminals also accept 2/0-500 kcmil.

Protection and control — integrated overload, brake output, diagnostics

Motor overload protection and intrinsic device protection are built in — no separate thermal relay or motor protection circuit breaker needed. Adjustable current limitation lets you set the starting torque profile to match the load, from 8% minimum load up to the rated current. A motor brake output is integrated — for hoist, incline, or fast-stop applications, the soft starter controls the brake directly without an external brake relay. Fault signals appear on the onboard display, reducing troubleshooting time. Maximum motor cable length is 500 m — sufficient for most plant layouts. Operating ambient up to 60°C with storage range -25 to +80°C covers non-conditioned plant floors.

Lifecycle and sourcing — current production, quoted to order

Sourced through independent distribution channels. No stock-holding claim; quoted per inquiry.

Frequently asked questions

What is the closest alternative to 3RW4456-2BC34 in the SIRIUS family?

No official pin-compatible alternative or successor is recorded for this order code. The 3RW4456-2BC34 occupies a specific current rating (1351 A at 40°C) and form factor within the SIRIUS soft starter range; a different current class would require a different frame size and mounting footprint.

What compliance documentation does Siemens provide for 3RW4456-2BC34?

The unit is designed to IEC 60947-4-2 (pollution degree 3) and carries the SIRIUS brand. Specific RoHS, REACH, UL, and CE declarations are available from Siemens documentation; no separate cert numbers are listed in the spec record.

What does the inside-delta circuit feature do on this soft starter?

Inside-delta connection reduces the current through the motor cables to 58% of the line current. For a 1351 A motor, that means the soft starter sees ~783 A per phase on the motor side, allowing smaller cable cross-sections or longer cable runs between the soft starter and the motor.

MPN
3RW4456-2BC34