Skip to main content
Siemens 3RW4466-2BC36 — Soft Starters

Siemens 3RW4466-2BC36 SIRIUS Soft Starter, 2103 A, 690 V

MPN3RW4466-2BC36

Siemens SIRIUS 3RW4466-2BC36 soft starter, 2103 A at 40 °C, 690 V insulation voltage, 50/60 Hz, integrated bypass contact system, inside-delta circuit capable.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW4466-2BC36 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW4466-2BC36 — Power & Motor Rating
ParameterValue
Rated operational current at 40 °C2 103A
Rated operational current at 50 °C1 864A
Rated operational current at 60 °C1 680A
Rated insulation voltage690V
Minimum settable current (% of Ie)8%

Control & Connection

3RW4466-2BC36 — Control & Connection
ParameterValue
Control supply voltage typeAC
Rated voltage at 50 Hz115V
Rated voltage at 60 Hz115V
Main circuit terminal typebusbar connection
Auxiliary contact rating (UL)B300 / R300
Control supply voltage tolerance, AC 50 Hz (max.)10%
Control supply voltage tolerance, AC 50 Hz (min.)-15%
Control supply voltage tolerance, AC 60 Hz (max.)10%
Control supply voltage tolerance, AC 60 Hz (min.)-15%
Control supply frequency tolerance (max.)10%
Control supply frequency tolerance (min.)-10%
Operating frequency tolerance (max.)10%
Operating frequency tolerance (min.)-10%
Operating voltage tolerance, inside-delta (max.)10%
Operating voltage tolerance, inside-delta (min.)-15%

Protection & Features

3RW4466-2BC36 — Protection & Features
ParameterValue
Motor overload protectionYes
Thermistor motor protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW4466-2BC36 — Mechanical
ParameterValue
Height780mm
Width575mm
Depth292mm
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100mm
Mounting clearance, bottom75mm
Mounting clearance, side5mm

Environmental

3RW4466-2BC36 — Environmental
ParameterValue
Operating temperature range60°C
Ambient class during operation (IEC 60721)3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Product details

Active production — current ratings and derating profile

The 3RW4466-2BC36: At 40 °C ambient it delivers 2103 A continuous; derate to 1864 A at 50 °C and 1680 A at 60 °C. The derating temperature threshold is 40 °C — above that the output current drops linearly, so the panel cooling design and ambient placement govern the real capacity. Rated operating frequency is 50/60 Hz at 115 V control supply, matching global line frequencies without a configuration change.

Bypass, inside-delta, and current limitation — what they mean for the motor circuit

An integrated bypass contact system is built in — once the motor reaches full speed, the thyristors are shorted, eliminating semiconductor conduction losses during run. This keeps the enclosure heat load down and avoids an external bypass contactor. Inside-delta circuit wiring is supported, which lets the soft starter control only two phases in a delta-configured motor, reducing the starter current rating to 58% of the motor FLA — a common technique for large motors where the starter frame size would otherwise jump. Adjustable current limitation is standard — set the start current between 100% and the unit's ceiling to match the load's breakaway torque requirement without tripping upstream protection.

Mounting, wiring, and panel integration constraints

Mounting position allows vertical surface installation with ±90° rotation and ±22.5° tilt forward/backward — useful when the panel depth forces a non-flat orientation. Dimensions are 780 mm high × 575 mm wide × 292 mm deep — this is a large-frame unit that needs its own backplate area. Clearance requirements: 100 mm above, 75 mm below, 5 mm at the sides for airflow and cable bending radius. Main current circuit termination is busbar connection; stranded cable range is 70–240 mm², finely stranded 50–240 mm², and AWG 2/0–500 kcmil.

Environmental ratings and protection features

Degree of pollution 3 per IEC 60947-4-2 — suitable for industrial environments where conductive dust or occasional condensation occurs. Storage temperature range is -25 to +80 °C; maximum operating ambient is 60 °C. Motor overload protection and intrinsic device protection (thyristor overtemperature, phase imbalance) are built in. A display provides fault signalling, and an external reset input allows remote clearing of trip conditions. A motor brake output is included as a product component, simplifying the wiring for applications that need a DC injection brake on the same contactor.

Frequently asked questions

What is the maximum motor cable length for 3RW4466-2BC36?

The maximum wire length is 500 m — this is the total run from the starter to the motor, not per phase. Longer runs may require output reactors to limit reflected-wave voltage stress on the motor insulation.

Does 3RW4466-2BC36 require an external bypass contactor?

No — the integrated bypass contact system handles full-speed running, so no external bypass contactor is needed. This saves panel space and wiring labour.

MPN
3RW4466-2BC36