Skip to main content
Siemens 3RW4466-2BC36

Siemens 3RW4466-2BC36 SIRIUS Soft Starter, 2103 A, 690 V

MPN 3RW4466-2BC36

Siemens SIRIUS 3RW4466-2BC36 soft starter, 2103 A at 40 °C, 690 V insulation voltage, 50/60 Hz, integrated bypass contact system, inside-delta circuit capable.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW4466-2BC36 specifications
ParameterValue
Mountingscrew fixing
Depth292 mm
Width575 mm
Height780 mm

Product details

Active production — current ratings and derating profile

The 3RW4466-2BC36: At 40 °C ambient it delivers 2103 A continuous; derate to 1864 A at 50 °C and 1680 A at 60 °C. The derating temperature threshold is 40 °C — above that the output current drops linearly, so the panel cooling design and ambient placement govern the real capacity. Rated operating frequency is 50/60 Hz at 115 V control supply, matching global line frequencies without a configuration change.

Bypass, inside-delta, and current limitation — what they mean for the motor circuit

An integrated bypass contact system is built in — once the motor reaches full speed, the thyristors are shorted, eliminating semiconductor conduction losses during run. This keeps the enclosure heat load down and avoids an external bypass contactor. Inside-delta circuit wiring is supported, which lets the soft starter control only two phases in a delta-configured motor, reducing the starter current rating to 58% of the motor FLA — a common technique for large motors where the starter frame size would otherwise jump. Adjustable current limitation is standard — set the start current between 100% and the unit's ceiling to match the load's breakaway torque requirement without tripping upstream protection.

Mounting, wiring, and panel integration constraints

Mounting position allows vertical surface installation with ±90° rotation and ±22.5° tilt forward/backward — useful when the panel depth forces a non-flat orientation. Dimensions are 780 mm high × 575 mm wide × 292 mm deep — this is a large-frame unit that needs its own backplate area. Clearance requirements: 100 mm above, 75 mm below, 5 mm at the sides for airflow and cable bending radius. Main current circuit termination is busbar connection; stranded cable range is 70–240 mm², finely stranded 50–240 mm², and AWG 2/0–500 kcmil.

Environmental ratings and protection features

Degree of pollution 3 per IEC 60947-4-2 — suitable for industrial environments where conductive dust or occasional condensation occurs. Storage temperature range is -25 to +80 °C; maximum operating ambient is 60 °C. Motor overload protection and intrinsic device protection (thyristor overtemperature, phase imbalance) are built in. A display provides fault signalling, and an external reset input allows remote clearing of trip conditions. A motor brake output is included as a product component, simplifying the wiring for applications that need a DC injection brake on the same contactor.

MPN
3RW4466-2BC36