Skip to main content
Siemens 3RW5055-2TB05 — Soft Starters

Siemens 3RW5055-2TB05 Soft Starter, 68 A, 200-600 V, ATEX

MPN3RW5055-2TB05
Active

Siemens 3RW5055-2TB05 soft starter, 68 A minimum, 200-600 V, ATEX, IECEx, trip class 10A/10E/20E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing, 249 x 120 x 198 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5055-2TB05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5055-2TB05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)75 kW
Rated motor power at 230 V (40 °C)37 kW
Rated operational current at 40 °C143 A
Rated operational current at 50 °C128 A
Rated operational current at 60 °C118 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 134 W
3RW5055-2TB05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
3RW5055-2TB05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5055-2TB05 — Mechanical
ParameterValue
Height198 mm
Width120 mm
Depth249 mm
Weight3.2 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5055-2TB05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; derating as of 1000 m, see Manual
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5055-2TB05 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (preset) / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases2
Utilization category according to IEC 60947-4-2AC-53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
Ramp-Down Time Of Soft Starter0 ... 20 s
3RW5055-2TB05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What the ATEX and IECEx ratings mean for your hazardous-area motor circuit

The 3RW5055-2TB05: This soft starter carries both ATEX and IECEx certification, meaning it is approved for installation in explosive atmospheres per the ATEX directive and the IECEx scheme — a requirement for motor starting in Zone 1 or Zone 2 gas environments or Zone 21/22 dust areas, depending on the full system certification. The trip class is preset to CLASS 10A / 10E, with a selectable CLASS 20E option per IEC 60947-4-2. CLASS 10A clears an overload in under 10 seconds at 7.2× Ie — fast enough to protect a standard motor winding during a stall without nuisance tripping on a normal start. Rated voltage covers 200 to 600 V, so it handles common low-voltage motor supplies from 208 V through 480 V and up to 600 V without a separate voltage tap.

Panel integration and mounting constraints

Mounting is by screw fixing — no DIN-rail clip. The unit measures 249 mm deep by 120 mm wide by 198 mm high, so plan for a backplate footprint that accommodates the depth plus the required clearance: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the side.

Fieldbus and control options for networked motor control

The soft starter supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET with PROFIenergy — covering the major industrial Ethernet and fieldbus protocols for integration into a PLC-based motor control center. Starting profiles include soft torque, voltage ramp, and pump ramp down — the pump ramp down feature is specifically for reducing water hammer on pump stop, a common requirement in water/wastewater applications. Remote reset is available by cycling the 24 V DC control supply, and auto-reset is configurable — useful for unattended installations where a manual reset after a fault is not practical.

Approvals include UL, CSA, and CE marking, so the part is accepted in North American and European regulatory jurisdictions without additional certification work.

MPN
3RW5055-2TB05