Siemens 3RW5072-2AB04 — Soft Starters

Siemens 3RW5072-2AB04 Soft Starter, 90 A, 200-480 V, ATEX

MPN3RW5072-2AB04
Active

Siemens 3RW5072-2AB04 soft starter, hybrid switching device, 90 A minimum, 200-480 V, ATEX, UKEX, IECEx, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5072-2AB04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5072-2AB04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)110 kW
Rated motor power at 230 V (40 °C)55 kW
Rated operational current at 40 °C210 A
Rated operational current at 50 °C186 A
Rated operational current at 60 °C170 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 867 W
3RW5072-2AB04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
3RW5072-2AB04 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5072-2AB04 — Mechanical
ParameterValue
Height230 mm
Width160 mm
Depth282 mm
Weight7.3 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5072-2AB04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; derating as of 1000 m, see Manual
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5072-2AB04 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (preset) / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases2
Utilization category according to IEC 60947-4-2AC-53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
Ramp-Down Time Of Soft Starter0 ... 20 s
3RW5072-2AB04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this soft starter handles — and where it fits

The Siemens 3RW5072-2AB04 is a hybrid switching device rated for a minimum operating current of 90 A across a voltage range of 200 to 480 V. The trip class is selectable between CLASS 10A, 10E (preset), and 20E per IEC 60947-4-2, which means you can match the thermal overload protection to the motor start profile — CLASS 10 for standard starts, CLASS 20 for higher-inertia loads like centrifuges or crushers. It carries ATEX, UKEX, and IECEx certification, so it can be integrated into motor starter assemblies in hazardous-area zones where explosive atmospheres may be present. The approvals cover the soft starter itself as part of a certified installation — the enclosure and cabling still need to match the zone classification. Fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET, with PROFIenergy available when used with the PROFINET communication module. This makes it straightforward to drop into an existing automation network without a separate gateway.

Mounting and environmental limits

The unit measures 160 mm wide by 230 mm high by 282 mm deep and uses screw fixing to a vertical mounting surface. The mounting position allows ±90° rotation and ±22.5° tilt forward/back, so it can be oriented to fit tight panel layouts without derating. Shock resistance is 15 g for 11 ms, dropping to 12 g if contact lifting is a concern — relevant for installations on vibrating machinery or near conveyors. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 0 mm backwards, and 5 mm at the sides. These are the minimum air gaps for heat dissipation and arc flash containment — don't crowd the enclosure.

Control and protection features

The soft starter includes voltage ramp and soft torque start profiles, plus a pump ramp-down function for reducing water hammer on pump stops. Auto-reset and remote reset (by cycling the control supply voltage) are supported, which is useful for unattended installations. An analog output is configurable as 4-20 mA (default) or 0-10 V when used with the High Feature HMI. The minimum load is 15% of the smallest settable Ie, so it can handle lightly loaded motors without nuisance tripping. An error logbook is available only with special accessories — factor that into the BOM if fault logging is required for compliance or diagnostics.

The 3RW5072-2AB04 carries UL, CSA, and CE markings, covering North American and European regulatory acceptance.

Frequently asked questions

What is the ATEX certification on this soft starter?

The 3RW5072-2AB04 carries ATEX, UKEX, and IECEx certification, meaning it is approved for use in motor starter assemblies within hazardous-area zones where explosive atmospheres may be present. The enclosure and field wiring must still match the zone classification.

What fieldbus protocols does the 3RW5072-2AB04 support?

It supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET. PROFIenergy is available when used with the PROFINET communication module.

What compliance documentation does Siemens provide for this soft starter?

The unit carries UL, CSA, and CE markings, plus ATEX, UKEX, and IECEx certifications. These cover North American and European regulatory acceptance as well as hazardous-location approvals.

MPN
3RW5072-2AB04