Skip to main content
Siemens 3RW5076-6AB15 — Soft Starters

Siemens 3RW5076-6AB15 Soft Starter, 200 A, ATEX, Active

MPN3RW5076-6AB15
Active

Siemens 3RW5076-6AB15 soft starter, 200 A minimum, 200-600 V, ATEX/UKEX/IECEx certified, trip class 10A/10E/20E, PROFIBUS/Modbus/EtherNet/IP, active production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5076-6AB15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5076-6AB15 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)250 kW
Rated motor power at 230 V (40 °C)132 kW
Rated operational current at 40 °C470 A
Rated operational current at 50 °C416 A
Rated operational current at 60 °C380 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)4 438 W
3RW5076-6AB15 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
3RW5076-6AB15 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5076-6AB15 — Mechanical
ParameterValue
Height230 mm
Width160 mm
Depth282 mm
Weight7.3 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5076-6AB15 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; derating as of 1000 m, see Manual
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5076-6AB15 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (preset) / 20E; acc. to IEC 60947-4-2; acc. to IEC 60947-4-2
Number Of Controlled Phases2
Utilization category according to IEC 60947-4-2AC-53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
Ramp-Down Time Of Soft Starter0 ... 20 s
3RW5076-6AB15 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Trip class and motor protection profile

The 3RW5076-6AB15: Trip class is selectable as CLASS 10A, 10E (preset), or 20E per IEC 60947-4-2. CLASS 10A suits standard motor starts with a short acceleration time; The preset 10E is a common middle ground for general-purpose pumps and fans. The soft starter supports voltage ramp, soft torque, and pump ramp down profiles — the pump ramp down feature gradually reduces voltage to prevent water hammer on stop, a specific need for wastewater and irrigation applications.

Fieldbus and control integration

Onboard fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP, plus PROFIenergy support when paired with the PROFINET communication module. This covers the major industrial Ethernet and serial networks, so the starter drops into most control architectures without a gateway. The analog output is configurable as 4-20 mA (default) or 0-10 V, parameterizable via the High Feature HMI accessory. Remote reset is available by cycling the control supply voltage — useful for unattended restart after a fault.

Mounting and environmental limits

Dimensions are 282 mm depth, 160 mm width, 230 mm height, with screw fixing to the mounting plate. Clearance requirements: 100 mm upwards, 10 mm forwards, 75 mm downwards, 5 mm at the sides — plan the enclosure layout accordingly to avoid derating from restricted airflow. Shock resistance is 15 g for 11 ms, with potential contact lifting at 12 g / 11 ms — the starter is mechanically robust for industrial environments but the contact lifting threshold matters for vibration-prone installations.

CE marking, UL approval, and CSA approval are all listed. ATEX, UKEX, and IECEx certifications are present for explosive atmosphere duty. The product category is hybrid switching devices — combines semiconductor and electromechanical switching for reduced heat dissipation during run.

Frequently asked questions

What ATEX and UKEX certifications does 3RW5076-6AB15 carry?

ATEX, UKEX, and IECEx certifications are all listed as Yes. This qualifies the soft starter for installation in Zone 1 or Zone 2 explosive gas atmospheres and Zone 21 or Zone 22 combustible dust areas, subject to the system-level ATEX directive compliance of the full panel.

MPN