Trip Class and Motor Protection Profile
The 3RW5077-2TB05 is a SIRIUS soft starter rated for a minimum set current of 240 A, with a rated operating voltage of 200 to 600 VAC. Its trip class is configurable as CLASS 10A, CLASS 10E (preset), or CLASS 20E, per IEC 60947-4-2.
Fieldbus and Communication Options
This unit supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard with PROFIenergy. The PROFIenergy function, available in conjunction with the PROFINET communication module, allows the soft starter to be placed into an energy-saving idle state during production pauses — useful on automated lines where the motor does not need to be ready to start between cycles. No analog output is fitted; torque control is not available on this variant.
Mounting, Environment, and Certifications
Screw-fixed, 160 mm wide, 230 mm high, 282 mm deep. Clearances: 100 mm up, 75 mm down, 10 mm forward, 0 mm back, 5 mm sides.